Welcome to our new website, found an issue or bug? Please report it here

ZW-ED-Series
ZW-ED Temperature Humidity & Barometric pressure transmitters
Models In Stock
Please see our XW-ED products as alternative
ZW-ED-Series
From
$
373.97
Models In Stock

Product Overview
This rugged high-performance and low power consumption OMEGA™ ZW-ED wireless sensor/transmitter system provides web-based monitoring temperature, humidity, and barometric pressure.
The radio is an IEEE 802.15.4 compliant transmitter operating at 2.4 GHz designed to transmit up to 1000m* (3280') outdoor and around 100m* (328') indoor to a ZW-REC coordinator. The ZW-REC connects directly to an Ethernet network to serve active web pages and display the data. You can monitor and record temperature, relative humidity, and barometric pressure over an Ethernet network with no special software—just your web browser.
OMEGA Enterprise Gateway
Software: OMEGA Enterprise Gateway
These wireless devices are designed for demanding industrial applications indoors and harsh outdoor environments. The electronics are protected in a rugged weatherproof polycarbonate NEMA 4 (IP65) rated housing. A variety of compatible probes are available to suit your application.
* Without obstructions or interference
Specifications
Input Types
Digital Probe Inputs: Temperature, Barometric Pressure, and Humidity
Local Display
Optional LCD Display:Displays Temperature in C, Pressure in mbar and Relative Humidity in % where applicable
EXTERNAL SENSOR SPECIFICATIONS
Environmental
Operating Conditions:
Base Unit: -20 to 70°C (-4 to 158°F), 90% RH non-condensing
CR2032 Battery: -20 to 60°C (-4 to 140°F), 90% RH non-condensing
Alkaline Battery: -18 to 55°C (-0.4 to 131°F), 90% RH non-condensing
LCD Option: -10 to 60°C (14 to 140°F), 90% RH non-condensing
Packaging
Enclosure Material: Polycarbonate
Enclosure Protection: NEMA 4 (IP65)
Enclosure Dimensions: 135.9 L x 82 W x 39 mm D (5.35 x 3.23 x 1.56")
General
Agency Approval: ECCN 5A992, EMC 2014/30/EU, LVD 2014/35/EU, RED 2014/53/EU, FCC ID T40JN5168M5
Software: Compatible with the OMEGA™ Dashboard
Note: Because of transmission frequency regulations, the ZW series products may only be used in the United States, Canada, Europe, China, Japan, Korea, and Brazil.
A Complete Wireless System Requires At Least:
One ZW End Device (ZW-ED), One Digital Probe (zTPx-P, ZTHPx-P or zBTx-P) and One ZW Coordinator/Receiver (ZW-REC). (Recommended)
Example: 3 ZW-ED, 3 zTP1-P and 1 ZW-REC for a 3 zone wireless temperature measurement system
The radio is an IEEE 802.15.4 compliant transmitter operating at 2.4 GHz designed to transmit up to 1000m* (3280') outdoor and around 100m* (328') indoor to a ZW-REC coordinator. The ZW-REC connects directly to an Ethernet network to serve active web pages and display the data. You can monitor and record temperature, relative humidity, and barometric pressure over an Ethernet network with no special software—just your web browser.

Software: OMEGA Enterprise Gateway
These wireless devices are designed for demanding industrial applications indoors and harsh outdoor environments. The electronics are protected in a rugged weatherproof polycarbonate NEMA 4 (IP65) rated housing. A variety of compatible probes are available to suit your application.
* Without obstructions or interference
Specifications
Input Types
Digital Probe Inputs: Temperature, Barometric Pressure, and Humidity
Local Display
Optional LCD Display:Displays Temperature in C, Pressure in mbar and Relative Humidity in % where applicable
EXTERNAL SENSOR SPECIFICATIONS

TEMPERATURE Accuracy/Range*: zTP1 (-P/-LCD/-DC/-CCELL); zTP2 (-P/-LCD/-DC/-CCELL) ±0.5°C for 10° to 85°C (±1°F for 50° to 185°F) ±1°C for -40° to 10°C and 85° to 125°C (±1.8°F for -40° to 50°F and 185° to 257°F) zBTHP (-P/-LCD/-DC/-CCELL); zTHP (-P/-LCD/-DC/-CCELL) zTHP2 (-P/-LCD/-DC/-CCELL) ±0.5°C for 5° to 45°C (±1°F for 41° to 113°F) up to 1.5°C for -40° to 5°C and 45° to 124°C (up to 2.7°F for -40° to 41°F and 113° to 255°F) refer to chart zBTP (-P/-LCD/-DC/-CCELL) ±0.8°C @ 20°C (±1.5°F @ 68°F) ±2°C for -40° to 85°C (±3.6°F for -40° to 185 °F) Resolution: 0.1°C Repeatablilty: ±0.1°C, for zBTHP, zTHP, zTHP2 (-P/-LCD/-DC/-CCELL), *Note: extended temperature ranges are for External Probes only Industrial Probe: SS 316 housing, 137mm x Ø16mm (5” x Ø 0.63”) for zBTP (-P/-LCD/-DC/-CCELL); zBTHP (-P/-LCD/-DC/-CCELL); zTHP (-P/-LCD/-DC/-CCELL) Short Probe, Quick Disconnect: SS 316 housing, 78mm x Ø16mm (3.1” x Ø 0.63”) for zTHP2 (-P/-LCD/-DC/-CCELL) Stick Probe: ABS tubing, 152.4 mm x Ø6.35 mm (6” x Ø 0.25”) for zTP1 (-P/-LCD/-DC/-CCELL) Lug Mounted Probe: Copper tubing, 53.4 mm x Ø 7.92mm (2.1” x Ø 0.312”); mounting hole Ø 4.72mm (Ø 0.186”) for zTP2 (-P/-LCD/-DC/-CCELL) Cable Dimensions and Operating Temperature: 3 m (10’) long x Ø 2.62 mm (0.103”) -80° to 200°C (-112° to 392°F) for zTHP (-P/-LCD/-DC/-CCELL); zTP1 (-P/-LCD/-DC/-CCELL); zTP2 (-P/-LCD/-DC/-CCELL) 3 m (10’) long x Ø 4.45 mm (0.175”) -55 to 105°C (-67 to 221°F) for zBTP (-P/-LCD/-DC/-CCELL); zBTHP (-P/-LCD/-DC/-CCELL) | RELATIVE HUMIDITY Accuracy/Range at 25°C-Non-Condensing: zBTHP (-P/-LCD/-DC/-CCELL); zTHP (-P/-LCD/-DC/-CCELL) ±2.75% for 10 to 90%; ±3% for 5 to 10% and 90 to 95%; ±4% for 0 to 5% and 95 to 100% Hysteresis: ±1% RH Non-linearity: ±3% Repeatability: ±0.1% Resolution: 0.1% BAROMETRIC PRESSURE Accuracy/Range: zBTP (-P/-LCD/-DC/-CCELL), zBTHP (-P/-LCD/-DC/-CCELL); ±2 mbar for 10 mbar to 1100 mbar (1 KPa to 110 KPa) Resolution: 0.1 mbar THERMOCOUPLE INPUT (Coming Soon) Temperature Range: refer to Thermocouple Chart Temperature Accuracy: refer to Thermocouple Chart Temperature Stability: 0.08°C/°C Temperature Coefficient: ±25 ppm/°C Thermocouple Cold End Tracking: 0.1°C/°C Thermocouple Lead Resistance: 100 ohm max. Thermocouple Type (ITS 90): J, K, T, E, R, S, B, C, N, L (DIN J) Warm-Up to Rated Accuracy: 30 minutes ANALOG VOLTAGE & CURRENT INPUT (Coming soon) Voltage Input: Differential; bipolar; ±100 mV, ±1 V, ±10 V Input Impedance: 400 K ohm for voltage Current Input: Differential; bipolar; ±20 mA (5 Ohm load) Accuracy: ±0.1% Full Range @ 25°C Reading Rate: Periodic (1 sample/update) or continuous (20 samples/second) A/D Conversion: Sigma-Delta Resolution: 16 bits Temperature Coefficient: ±50 ppm/°C Common Mode Rejection: 105 dB Normal Mode Rejection: 98 dB Warm-Up to Rated Accuracy: 30 minutes |
Environmental
Operating Conditions:
Base Unit: -20 to 70°C (-4 to 158°F), 90% RH non-condensing
CR2032 Battery: -20 to 60°C (-4 to 140°F), 90% RH non-condensing
Alkaline Battery: -18 to 55°C (-0.4 to 131°F), 90% RH non-condensing
LCD Option: -10 to 60°C (14 to 140°F), 90% RH non-condensing
Packaging
Enclosure Material: Polycarbonate
Enclosure Protection: NEMA 4 (IP65)
Enclosure Dimensions: 135.9 L x 82 W x 39 mm D (5.35 x 3.23 x 1.56")
General
Agency Approval: ECCN 5A992, EMC 2014/30/EU, LVD 2014/35/EU, RED 2014/53/EU, FCC ID T40JN5168M5
Software: Compatible with the OMEGA™ Dashboard
Note: Because of transmission frequency regulations, the ZW series products may only be used in the United States, Canada, Europe, China, Japan, Korea, and Brazil.
A Complete Wireless System Requires At Least:
One ZW End Device (ZW-ED), One Digital Probe (zTPx-P, ZTHPx-P or zBTx-P) and One ZW Coordinator/Receiver (ZW-REC). (Recommended)
Example: 3 ZW-ED, 3 zTP1-P and 1 ZW-REC for a 3 zone wireless temperature measurement system
Show Ratings & Reviews
Is it possible to connect a K type thermocouple ? this same thermocouple have a wire of 50' long do the ZW-ED will be able to give enought power for reading after 50' long ?
Thank you for your question. The ZW-ED series does not support thermocouples. Please see XW-EDA series that will support thermocouples with 50 ft leads.
https://www.omega.com/en-us/iiot-wireless-systems/wireless-transmitters/xw-eda-series/p/XW-EDA?searchterm=XW-EDA
Date published: 2021-10-14
How is it calibrated?
Thank you for your question. Unit is calibrated at the factory by Omega.
Date published: 2021-10-19