Skip to search Skip to main content Skip to navigation

Welcome to our new website, found an issue or bug? Please report it here

We noticed you are from . Visit your local site for regional offers and live support.

CMS300

$247.25

Item# CMS300

In Stock

Lead Time (If not in stock): 0 week

Product Specs

<< See all Product Models
Brand
Accuracy ± 5 ppm or 5 %
Calibration Option N/A
Compliance CE, UL
Compliance Note Sensor is UL recognized component for ANSI/UL-2034, UL-2075, E340403, CE
Coverage Area 7500 sq ft
Display Type N/A
Drift <5%/Year in Air
Enclosure Type IP64
Gas Concentration 0 to 300 ppm
Materials Glass-Filled Polycarbonate
Operating Temperature, Max 122 °F
Operating Temperature, Min -4 °F
Output Detail Jumper selectable 4-20 mA (loop powered) or 2-10 V (max. load 2 kΩ)
Output Signal Current, Voltage
Relative Humidity 15 to 90% RH Constant, 0 to 99% RH Intermittent
Relay Output Factory Set for Direct Acting
Resolution 1 ppm
Response Time <45 s to 90%
Sensor Life 5 Years
Sensor Type Electrochemical
Set Point Selectable 25, 60, or 150 PPM
Set Point Differential/Hysteresis 3 % scale
Storage Temperature, Max 68 °F
Storage Temperature, Min 32 °F
Switch Rating NO: 5 A @ 30 Vdc, 250 Vac; NC: 3 A @ 30 Vdc, 250 Vac
Switch Type SPDT NO/NC, Selectable
Temperature Effect ± 2% Over Range
Weight 1 lb
Zero Setting Adjustable Range 15 Turn Potentiometers
See All Specs Show Less