Skip to search Skip to main content Skip to navigation

1-800-663-4209 | Your feedback matters, take a quick survey Website Feedback

We noticed you are from . Visit your local site for regional offers and live support.

Model-CDSN

CO2 Transmitter with Temp Monitoring, LEED® Certified, Universal Output

  • Minimize inventory and save time by combining CO2 and temperature measurement, as well as DIP switch selectable current/voltage outputs
  • Integral passive temperature reduces the number of devices mounted in the space
  • Requires minimal maintenance with Automatic Baseline Correction (ABC) to account for sensor drift
  • Reduce operation costs using a low energy, reliable, and repeatable CO2 sensor
  • Simplify installation with backplate electrical connections
Model-CDSN
From $ 209.00
CO2 Transmitter with Temp Monitoring, LEED® Certified, Universal Output Model-CDSN Model-CDSN
loading all models
Product Overview
  • Applications HVAC
  • Carbon Dioxide Accuracy ± 40 PPM + 3% rdg
  • Carbon Dioxide Concentration, Max 2000 ppm
  • Carbon Dioxide Concentration, Min 0 ppm
  • Carbon Dioxide Response Time 120 s (τ90)
  • Compliance CE
  • Display Type N/A
  • Electrical Connection Screw Terminal
  • Electrical Output 0 to 20 mA
  • Enclosure Ratings IP30, NEMA Type 1
  • Materials ABS
  • Mounting Orientation N/A
  • Operating Temperature, Max 122 °F
  • Operating Temperature, Min 32 °F
  • Output Detail Field selectable; Current: 4-20 mA or 0-20 mA; Voltage: 0-5 V, 1-5 V, 0-10 V, or 2-10 V
  • Output Signal Current, Voltage
  • Relative Humidity 0 to 85% RH Non-Condensing
  • Sensor Life 15 Years
  • Sensor Type NDIR
  • Storage Temperature, Max 158 °F
  • Storage Temperature, Min -22 °F
  • Supply Power Note ± 20%, 50/60 Hz
  • Supply Power Type AC/DC
  • Supply Voltage 24 Vac/Vdc
  • Switch Type N/A
  • Temperature Accuracy ± 1 °C
  • Temperature Output Range N/A
  • Voltage Output Range 0 to 5 V, 1 to 5 V, 0 to 10 V, 2 to 10 V
  • Warm Up Time <2 mins Operational; 10 mins Max Accuracy

The Model CDSN Carbon Dioxide Transmitter accurately monitors the CO2 concentration and temperature in schools, office buildings, and other indoor environments to help achieve LEED® certification and energy savings. In order to achieve a higher level of accuracy, the Model CDSN includes digital barometric pressure adjustment. The CO2 universal output allows users to select the transmitter output to be 4-20 mA, 0-5 VDC, or 0-10 VDC to work with virtually any building management controller. In addition, the housing security feature reduces the likelihood of physical tampering.

California Residents: Click Here for Proposition 65 WARNING.

Product Applications

  • Demand control ventilation in schools
  • Indoor air quality monitoring in office buildings
  • bvseo_sdk, java_sdk, bvseo-4.0.0
  • CLOUD, getReviews, 22ms
  • REVIEWS, PRODUCT
  • bvseo-msg: The resource to the URL or file is currently unavailable.;
  • bvseo_sdk, java_sdk, bvseo-4.0.0
  • CLOUD, getContent, 53ms
  • QUESTIONS, PRODUCT
  • bvseo-msg: The resource to the URL or file is currently unavailable.;
en-US
en
Save Configuration