DRST-UR-Univ-Sig-Cond

DIN Rail Universal Programmable Signal Conditioner w/ Relay Output

Models In Stock
  • Input for RTD, TC, O, potentiometer, mA and V
  • 2-wire supply 16 V
  • UL and cUL Approval
  • Output for current, voltage and 2 relays
DRST-UR-Univ-Sig-Cond
From $ 335.04
Models In Stock
DIN Rail Universal Programmable Signal Conditioner w/ Relay Output DRST-UR-Univ-Sig-Cond DRST-UR-Univ-Sig-Cond
loading all models
Product Overview
  • Accuracy ± 0.1 %
  • Approvals UL: UL 508/C22.2 no. 14; DNV-GL Marine Stand. f. Certific. No. 2.4; EU RO Mutual Recognition Type; Approval: MRA000000Z SIL Hardware assessed for use in SIL applications; Authority Requirements:EMC: 2014/30/EU, LVD: 2014/35/EU, EAC: TR-CU 020/2011
  • Calibration Temperature, Max 28 °C
  • Calibration Temperature, Min 20 °C
  • Cold Junction Compensation 20 to 28°C = ±1°C, -20 to 20°C/28 to 70°C = 2°C
  • Electrical Output 0 to 20 mA, 0 to 10 Vdc
  • EMC Immunity Note Standard EMC Imunity: <±0.5% of span; Extended EMC Immunity: NAMUR, NE21, A Criterion, Burst: <±1% of span; Wire Size: 1 x 2.5 mm²
  • EMC Standard EN61010-1, EN61326-1
  • Enclosure Ratings IP20
  • Fuse Rating 250 Vac/400 mA
  • Height 109 mm
  • Input Control Signal 0 to 12 Vdc
  • Input Control Signal Note Measurement Range: 0 to 12 Vdc; Programmable Measurement Ranges: 0/0.2 to 1, 0/1 to 5, 0/2 to 10 Vdc
  • Input Current 0 to 20 mA
  • Input_Current Note Programmable Measurement Ranges: 0 to 20 and 4 to 20 mA; Input Resistance: Nom. 20 Ω + PTC 50 Ω Sensor Error Detection: Loop; Break 4 to 20 mA: Yes
  • Input Resistance Voltage : Nom. 10 MΩ,Current: Nom. 20 Ω + PTC 50 Ω
  • Isolation Test/Working: 2.3 kVac/250Vac
  • Length 104 mm
  • Operating Temperature, Max 60 °C
  • Operating Temperature, Min -20 °C
  • Output Detail Signal Range: 0 to 20 mA; Programmable Signal Ranges: 0 to 20/4 to 20/20 to 0/20 to 4 mA; NAMUR NE43 Upscale/Downscale: 23 mA/3.5 mA; Output Limitation, on 4 to 20 and 20 to 4 mA signals: 3.8 to 20.5 mA; Output Limitation, on 0 to 20 and 20 to 0 mA signals: 0 to 20.5 mA; Signal Range: 0 to 10 Vdc; Programmable Signal Ranges: 0/0.2 to 1; 0/1 to 5 ; 0/2 to 10; 1 to 0.2/0; 5 to 1/0; 10 to 2/0 V
  • Output Signal Current, Voltage, 2 Relays
  • Potentiometer Input Range 10 to 100 kΩ
  • Power Consumption 2.5 W
  • Relative Humidity < 95% RH Non-Condensing
  • Relay Output 2 A @ 250 Vac
  • Relay Output Note Relay Functions: Setpoint, Window, Sensor error, Latch, Power and Off
  • Response Time 1 sec
  • Response Time Note Thermocouple: 1 sec, Current/Voltage: 400msec
  • RTD Input Note Effect of Sensor Cable Resistance: < 0.002 Ω/Ω (3/4-wire); Cable Resistance, Per Wire: 50 Ω; Sensor Current: 0.2 mA; Short Circuit Protection: < 15 Ω; Sensor Error Current: 2 µA / 0 µA
  • RTD Type 10/20/50/100/200/250/300/400/500/1000 Ω Pt Sensor, 50/100/120/1000 Ω Ni Sensor, 10/20/50/100 Ω Cu Sensor
  • Screw Terminal Torque 0.5 Nm
  • Sensor/Transmitter Power 25 to 16 Vdc/0 to 20 mA
  • Signal/Noise Ratio > 60 dB
  • Storage Temperature, Max 85 °C
  • Storage Temperature, Min -20 °C
  • Supply Power Note 21.6 to 253 Vac, 50 to 60 Hz or 19.2 to 300 Vdc
  • Supply Power Type AC/DC
  • Supply Voltage 21.6 to 253 Vac, 19.2 to 300 Vdc
  • Temperature Coefficient ≤±0.01% of span/°C
  • Temperature Measurement Range J: -100 to 1200°C, K: -180 to 1370 °C, T: -200 to 400 °C, E: -100 to 1000 °C, R: -50 to 1760 °C, S: -50 to 1760 °C, N: -180 to 1300 °C, B: 0 to 1820 °C, W3: 0 to 2300 °C, W5: 0 to 2300 °C, L: -200 to 900 °C, LR: -200 to 800 °C, RTD: -200 to 850 °C
  • Thermocouple Type J, K, T, E, R, S, B, C, N, L, U, D, LR
  • Vibration ±0.7 g
  • Vibration Note IEC 60068-2-6; 2 to 13.2 Hz: ±1 mm; 13.2 to 100 Hz: ±0.7 g
  • Weight 170 g
  • Width 23.5 mm
  • Wire Type Stranded
Advanced Features
Programmable via detachable display front, process calibration, signal and relay simulation, password protection, error diagnostics and selection of help text in several languages.
Application
• Linearized, electronic temperature measurement with RTD or TC sensor.
• Conversion of linear resistance variation to a standard analog current/voltage signal, i.e. from solenoids and butterfly valves or linear movements with attached potentiometer.
• Power supply and signal isolator for 2-wire transmitters. Process control with 2 pairs of potential-free relay contacts and analog output.
• Galvanic separation of analog signals and measurement of floating signals.
• The DRST-UR is designed according to strict safety requirements and is therefore suitable for application in SIL 2 installations.
Technical Characteristics
• When DRST-UR is used in combination with the DRSL-DISPLAY programming front, all operational parameters can be modified to suit any application. As the DRST-UR is designed with electronic hardware switches, it is not necessary to open the device for setting of DIP-switches.
• A green/red front LED indicates normal operation and malfunction. A yellow LED is ON for each active output relay.
• A continuous check of vital stored data for safety reasons.
• 4-port 2.3 kVAC galvanic isolation.

Environmental Conditions
Operating Temperature: -20 to 60°C
Storage Temperature -20 to 85°C
Calibration Temperature20 to 28°C
Relative Humidity < 95% RH (non-cond.)
Protection Degree IP20
Mechanical Specifications
Dimensions (H x W x D): 109 x 23.5 x 104 mm
Dimensions (H x W x D) w/ 4501/4511:109 x 23.5 x 116 / 131 mm
Weight Approx: 170 g
Weight incl. 4501 / 4511 (approx.): 185 g/270 g
Wire Size: 1 x 2.5 mm2 stranded wire
Screw Terminal Torque: 0.5 Nm
Vibration: IEC 60068-2-6
2 to 13.2 Hz: ±1 mm
13.2 to 100 Hz: ±0.7 g
Common Specifications
Supply
Supply Voltage, Universal: 21.6 to 253 Vac, 50 to 60 Hz or 19.2 to 300 Vdc
Fuse: 400 mA SB/250 Vac
Max. Required Power: = 2.5 W
Isolation Voltage
Isolation Voltage, Test/Working: 2.3 k Vac/250 Vac
Response Time
Temperature Input (0 to 90%, 100 to 10%) = 1 s
mA/V Input (0 to 90%, 100 to 10%): = 400 ms
Auxiliary Supplies
2-w. supply (term. 44...43): 25 to 16 Vdc / 0 to 20 mA
Programming Communication enabler DRSL-DISPLAY
Signal/Noise Ratio: Min. 60 dB (0 to 100 kHz)
Accuracy Better than 0.1% of sel. range
EMC Immunity Influence < ±0.5% of span
Extended EMC Immunity: NAMUR NE21, A Criterion, Burst: < ±1% of span
Input specifications
RTD input
RTD Type:
Pt10/20/50/100/200/250;
Pt300/400/500/1000;
Ni50/100/120/1000;
Cu10/20/50/100
Cable Resistance per Wire 50 Ω (max.)
Sensor Current: Nom. 0.2 mA
Effect of Sensor Cable Resistance (3/4-Wire): < 0.002 Ω/Ω
Sensor Error Detection: Yes
Short Circuit Detection: < 15 Ω
Linear Resistance Input
Linear Resistance Min/Max: 0 to 10000 Ω Potentiometer Input
Potentiometer Min/Max: 10 Ω to 100 kΩ
TC Input
Thermocouple Type: B, E, J, K, L, N, R, S, T, U, W3, W5, LR
Cold Junction Compensation (CJC) via ext. Sensor in Connector 5910: 20 to 28°C = ±1°C, -20 to 20°C/28 to 70°C = 2°C
CJC via int. Mounted Sensor: ±(2.0°C + 0.4°C * ∆t)
∆t =: Internal temp.-ambient temp.
Sensor Error Detection: Yes
Sensor Error Current: When
Detecting/Else: Nom. 2 µA / 0 µA
Current Input
Measurement Range: 0 to 20 mA
Programmable Measurement Ranges: 0 to 20 and 4 to 20 mA
Input Resistance: Nom. 20 Ω + PTC 50 Ω Sensor Error Detection: Loop
Break 4 to 20 mA: Yes
Voltage Input
Measurement Range 0 to 12 Vdc
Programmable Measurement Ranges: 0/0.2 to 1, 0/1 to 5, 0/2 to 10 Vdc
Input Resistance: Nom. 10 MΩ
Output Specifications
Current Output
Signal Range: 0 to 20 mA
Programmable Signal Ranges: 0 to 20/4 to 20/20 to 0/20 to 4 mA
Load (@ Current Output): ≤ 800 Ω
Load Stability: ≤ 0.01% of span/100 Ω
Sensor Error Indication: 0/3.5/23 mA/none
NAMUR NE43 Upscale/Downscale:23 mA/3.5 mA
Output Limitation, on 4 to 20 and 20 to 4 mA Signals: 3.8...20.5 mA
Output Limitation, on 0 to 20 and 20 to 0 mA Signals: 0 to 20.5 mA
Current Limit:≤ 28 mA
Voltage Output
Signal Range: 0 to 10 Vdc
Programmable Signal Ranges: 0/0.2 to 1; 0/1 to 5 ; 0/2 to 10; 1 to 0.2/0; 5 to 1/0; 10 to 2/0 V
Load (@ Voltage Output): ≥ 500 kΩ
Relay Output
Relay Functions: Setpoint, Window, Sensor error, Latch, Power and Off
Max. Voltage: 250 VRMS
Max. Current:2 AAC or 1 ADC
Max. AC Power: 500 VA
Observed Authority Requirements
EMC: 2014/30/EU
LVD: 2014/35/EU
EAC:TR-CU 020/2011
Approvals
UL: UL 508/C22.2 no. 14
DNV-GL Marine Stand. f. Certific. No. 2.4
EU RO Mutual Recognition Type
Approval: MRA000000Z
SIL Hardware assessed for use in SIL applications
  • bvseo_sdk, java_sdk, bvseo-4.0.0
  • CLOUD, getReviews, 2ms
  • REVIEWS, PRODUCT
  • bvseo-msg: The resource to the URL or file is currently unavailable.;
  • bvseo_sdk, java_sdk, bvseo-4.0.0
  • CLOUD, getContent, 25ms
  • QUESTIONS, PRODUCT
  • bvseo-msg: The resource to the URL or file is currently unavailable.;
en-US
en
Save Configuration