ITHX-D3-Series
DIN Rail Mount Temperature and Humidity Virtual Chart Recorder
- Web Server
- Alarms by Email or Text Message
- Accurate Readings
- Data Logging
ITHX-D3-Series
From
$
476.79

Product Overview
- Accuracy Note Temperature: ± 0.5°C for 5 to 45°C; up to ± 1.5°C for -40 to 5°C and 45 to 124°C, Accuracy/Range at 25°C: Non-Condensing: 10 to 90%: 2.75% RH, 5 to 10% and 90 to 95%: ± 3%, 0 to 5% and 95 to 100%: ± 4%
- Approvals CE, FCC-B
- Cable Temperature, Max 125 °C
- Cable Temperature, Min -40 °C
- Configuration Internal Web UI
- Data Interface Ethernet
- Data Interface Note Ethernet : (RJ45) Fixed or auto negotiating 10/100BASE-T, AUTO MDI/MDIX Supported Protocols:TCP, UDP, SNMP, SMTP, NTP, ARP, ICMP, DHCP, DNS, HTTP, and Telnet
- Electrical Connection Stripped Leads
- Form factor DIN rail mount
- Height 0.99 in
- Hysteresis ± 1% RH
- Input Type External
- Length 3.54 in
- Logging Modes Fixed interval
- Measurement Type Relative Humidity, Temperature
- Non-Linearity ± 3%
- Operating Temperature, Max 85 °C
- Operating Temperature, Min -40 °C
- Probe Diameter 0.63 in
- Probe Length 5 in
- Probe Style Industrial Probe
- Relative Humidity Accuracy ± 1.5 °C
- Repeatability ± 0.1%
- Response Time Temperature: 5 to 30 sec, RH: 8 sec
- Response Time Note Temperature: 5 to 30 seconds, tau 63%, RH: 8 seconds, tau 63%
- RH Measurement Range 0 to 100% RH
- Sensor Type Screw Terminal
- Software OPC Server; macro for data logging in Excel program; compatible with Windows® operating systems
- Storage Temperature, Max 125 °C
- Storage Temperature, Min -40 °C
- Supply Power Note 10 to 32 Vdc switching power supply (sold separately)
- Supply Power Type DC
- Supply Voltage 10 to 32 Vdc
- Temperature Accuracy ± 0.5 °C
- Temperature Measurement, Max 124 °C
- Temperature Measurement, Min -40 °C
- Temperature Repeatability ± 0.1 °C
- Weight 0.68 lb
- Width 4.53 in
View Temperature and Humidity with a Web Browser
The OMEGA™ iTHX transmitter lets you monitor and record temperature, relative humidity, and dew point over an Ethernet network or the Internet with no special software except a web browser. The iTHX serves active web pages to display realtime readings, charts of temperature and humidity, or log data in standard data formats for use in a spreadsheet or data acquisition program such as Excel or Visual Basic.
The virtual chart viewed on the web page is a JAVA™ Applet that records a chart over the LAN or Internet in real time. With the iTHX, there is no need to invest time and money learning a proprietary software program to log or chart the data.
Email Alarms
All iTHX models that are on a LAN that is connected to the Internet can trigger an alarm that can be sent by email to a user or a distribution list anywhere in the world, including text messages to cell phones and PDA’s.
Typical Applications
The iTHX is great for monitoring temperature and humidity in applications such as: clean rooms, computer rooms, HVAC systems, pharmaceutical and food processing and storage, hospitals, laboratories, semiconductor labs, electronic assembly, warehousing, museums, manufacturing, greenhouses and, farm animal shelters.
The OMEGA™ iTHX transmitter lets you monitor and record temperature, relative humidity, and dew point over an Ethernet network or the Internet with no special software except a web browser. The iTHX serves active web pages to display realtime readings, charts of temperature and humidity, or log data in standard data formats for use in a spreadsheet or data acquisition program such as Excel or Visual Basic.
The virtual chart viewed on the web page is a JAVA™ Applet that records a chart over the LAN or Internet in real time. With the iTHX, there is no need to invest time and money learning a proprietary software program to log or chart the data.
Email Alarms
All iTHX models that are on a LAN that is connected to the Internet can trigger an alarm that can be sent by email to a user or a distribution list anywhere in the world, including text messages to cell phones and PDA’s.
Typical Applications
The iTHX is great for monitoring temperature and humidity in applications such as: clean rooms, computer rooms, HVAC systems, pharmaceutical and food processing and storage, hospitals, laboratories, semiconductor labs, electronic assembly, warehousing, museums, manufacturing, greenhouses and, farm animal shelters.