Skip to search Skip to main content Skip to navigation

Welcome to our new website, found an issue or bug? Please report it here

We noticed you are from . Visit your local site for regional offers and live support.

DRSL-TEMP

$184.75

Item# DRSL-TEMP

Volume discounts available
Volume Discount Schedule
Quantity Price each
1-4 $184.75
5-9 $175.51
10-24 $171.82
25-49 $164.43
50-99 $160.73
100+ $157.04

In Stock

Lead Time (If not in stock): 24 weeks

Product Specs

<< See all Product Models
Brand
Accuracy Note Thermocouple Input: Better than 0.5°C or ±0.05% of span (selected input range) RTD Input: Better than 0.1°C or ±0.05% of span (selected input range)
Approvals CE, UL, RoHS
Calibration Temperature, Max 28 °C
Calibration Temperature, Min 20 °C
EMC Immunity Note NAMUR NE 21, A Criterion, Burst: <±1% of span (span = selected input range)
EMC Standard NAMUR NE 21
Electrical Output 4 to 20 mA
Enclosure Ratings IP20
Height 113 mm
Input Range Note THERMOCOUPLE INPUT ;Sensor and Cable Specifications:5 kΩ per wire;Cold Junction Compensation (CJC): Internal or external (selectable); CJC Accuracy via External CJC (Pt100 RTD Sensor): Better than ±0.15°C; CJC via Internally Mounted Sensor: Better than ±2.5°C;Open Thermocouple Detection: Yes (DIP switch selectable upscale or downscale);Pt100 RTD INPUT;Sensor Current, RTD: <150 µA;Sensor Cable Specifications:50 Ω per wire;Effect of Sensor Cable Resistance (3 or 4-Wire RTD): <0.002 Ω/Ω;Broken Sensor Detection: >800 Ω;Shorted Sensor Detection: <18 Ω
Input Type Thermocouple, RTD
Installation Pollution degree 2 and measurement/overvoltage category II
Isolation 300 Vac
Length 115 mm
Load Resistance Resistance: ≤(Vsupply - 5.5)/0.023
Mounting DIN Rail 35 mm Standard, EN 60715
Noise Calibration >60 dB
Number of Inputs 2
Operating Temperature, Max 70 °C
Operating Temperature, Min -25 °C
Output Detail Programmable Signal Ranges:0 to 20 mA and 4 to 20 mA Range Limits (NAMUR NE43 Out of Range): Below 3.8 mA or above 20.5 mA Sensor Error Detection(Dip Switch Selectable forEnable or None): Below 3.5 mA or above 23 mA Incorrect DIP-Switch Setting Identification: Below 3.5 mA Output Error Level: DIP switch selectable for upscale or downscale
Output Signal Current
Output Value Process
Power Consumption 0.7 W
RTD Accuracy ± 0.05 %
Relative Humidity 0 to 95% RH (non-condensing)
Response Time < 30 ms
Response Time Note Response Time (0 to 90%, 100 to 10%): <30 ms/300 ms (selectable, provides either fast response or signal dampening as needed)
Screw Terminal Torque 0.5 Nm
Stability Load Stability: ≤0.01% of span/100 Ω
Storage Temperature, Max 85 °C
Storage Temperature, Min -40 °C
Supply Power Type DC
Supply Voltage 5.5 to 35 Vdc
Temperature Coefficient Thermocouple : ≤±0.1°C/°C or ≤±0.01%/°C; RTD : ≤±0.02 °C/°C
Temperature Measurement Range J: -100 to 1200°C, K: -180 to 1372°C, Pt100: -200 to 850°C
Thermocouple Accuracy ± 0.05 %
Voltage Loss 5.5 Vdc
Weight 70 g
Width 6.1 mm
Wire Code Option 2 -, 3 - , 4- Wire
Wire Gauge 26 to 12 AWG
See All Specs Show Less