Product Overview
- Accuracy ± 0.05 %
- Additional Features 1 Explosion Proof Aluminum/Stainless Steel Housing
- Approvals EU RO Mutual Recognition Type; Approval: MRA0000009; ATEX 2014/34/EU: DEKRA 15 ATEX 0058 X; IECEx: IECEx DEK 15.0039 X; FM: FM16US0009X/FM16CA0010X; CSA: 70024231 EAC Ex TR-CU 012/2011: RU C-DK.GB08.V.01316; INMETRO: DEKRA 15.0014 X; NEPSI: GYJ15.1336X, GYJ15.1337X and GYJ15.1338X; SIL: Hardware assessed for use in SIL applications Authority Requirements: EMC: 2014/30/EU, EAC: TR-CU 020/2011
- Calibration Adjustment ± 50 % Max
- Calibration Temperature, Max 28 °C
- Calibration Temperature, Min 20 °C
- Data Interface HART 7, HART 5
- Dimensions Note Aluminum: 109.3 H x 145 W x 126 D mm, Stainless: 107.4 H x 145 W x 124 D mm Dimensions: Ø 110 mm
- Display LCD
- Display Note 96 x 64 pixels Resolution, Selectable ON/OFF and Selectable white or red colour Backlight Number of Digits: 5
- Electrical Output 4 to 20 mA
- EMC Immunity Note Standard EMC Imunity: <±0.1% of span; Extended EMC Immunity: NAMUR, NE21, A Criterion, Burst: <±1% of span; Wire Size: 0.13 x 1.5 mm²
- EMC Standard EN61010-1, EN61326-1
- Enclosure Ratings IP54, IP66, IP68, NEMA Type 4X
- Height 109 mm
- Input Control Signal -800 to 800 mV
- Input Control Signal Note Min. Measurement Range (Span): 2.5 mV
- Input Resistance 10 MΩ
- Isolation Test/Working: 1.5 kVac/50Vac
- Length 104 mm
- Load Resistance ≤ (Vsupply - 12) / 0.023 Ω
- Long Term Stability ±0.1% of span/year
- Operating Temperature, Max 85 °C
- Operating Temperature, Min -40 °C
- Operating Temperature Note -40 to 85°C (with Silicone O-ring),-20 to 85°C (with FKM Oring)
- Output Detail Signal Range: 4 to 20 mA,Min. Signal Range: 6 mA,NAMUR NE43 Upscale/Downscale: 23 mA/3.5 mA
- Output Load ≤ (Vsupply - 10) / 0.023 Ω
- Output Signal Current
- Potentiometer Input Range 0 to 7000 Ω
- Programmable Functions HART Setup
- Relative Humidity 0 to 100% RH Condensing
- Resolution Input Signal Dynamics: 22 bit; Output Signal Dynamics: 16 bit
- Response Time 1 to 60 sec; Update Time : 440 msec
- RTD Input Note Cable Resistance, Per Wire: 50 Ω; Sensor Current: 0.2 mA
- RTD Type 50/100/200/250/500/1000 Ω Pt Sensor, 50/100/120/1000 Ω Ni Sensor
- Screw Terminal Torque 0.4 Nm
- Sensor Break Detection Programmable 3.5 to 23 mA
- Signal/Noise Ratio > 60 dB
- Start Up Time 5 Sec
- Storage Temperature, Max 85 °C
- Storage Temperature, Min -40 °C
- Supply Power Note Intrinsically Safe: 10 (12 - with backlight)...30 Vdc, Other: 10 (12 - with backlight)...35 Vdc
- Supply Power Type DC
- Supply Voltage 10 to 30 Vdc
- Temperature Measurement Range J: -100 to 1200°C, K: -180 to 1370 °C, T: -200 to 400 °C, E: -100 to 1000 °C, R: -50 to 1760 °C, S: -50 to 1760 °C, N: -180 to 1300 °C, B: 0 to 1820 °C, W3: 0 to 2300 °C, W5: 0 to 2300 °C, L: -200 to 900 °C, LR: -200 to 800 °C, RTD: -200 to 850 °C
- Thermocouple Type J, K, T, E, R, S, B, C, N, L, U, D, LR
- Vibration ±4g
- Vibration Note EC 60068-2-6; 2 to 25 Hz: ±1.6 mm; 25 to 100 Hz: ±4 g
- Weight 1.3 kg
- Weight Note Aluminum: 1.3, Stainless: 2.8
- Width 23.5 mm
- Wire Type Stranded
Description
High Definition Display• 0, 90, 180, & 270 degree position adjustments.
• Monitoring, programming, and diagnostics view.
• Extensive diagnostics with flashing red or white backlight
• Supports 7 languages
Local operator interface (LOI)
• 3 optical buttons up, down and enter.
• Dynamically adaptive to wear or accumulation of dirt.
• Immune to interference from ambient light sources.
• Useable with or without gloves.
Configuration
• From the LOI through guided user menu.
• OMSET and HART modem.
• HHC, DCS or AMS via HART.
Mounting/Installation
• For installation in zone 0, 1, 2 and zone 20, 21, 22 and in Class 1, Division 1 and 2 applications.
• Hardware assessed for use in SIL 2 applications.
• Mounting on 1.5† † “2† pipe bracket or on wall / bulkhead.
Application
• Linearized temperature measurement with TC and RTD sensors e.g. Pt100 and Ni100.
• HART communication and 4...20 mA analog PV output for individual, difference or average temperature measurement of up to two RTD or TC input sensors.
• Conversion of linear resistance to a standard analog current signal, e.g from valves or Ohmic level sensors.
• Amplification of bipolar mV signals to standard 4...20 mA current signals.
• Up to 63 transmitters (HART 7) can be connected in a multidrop communication setup.
Technical Characteristics
• NAMUR NE43 and NE89.
• HART protocol revision can be changed by user configuration to either HART 5 or HART 7 protocol.
Specifications
Environmental Conditions
Operating Temperature: -40 to 85 °C (with silicone O-ring)
Operating Temperature: -20 to 85 °C (with FKM Oring)
Storage Temperature: -40 to 85 °C
Calibration Temperature: 20 to 28 °C
Relative Humidity: 0 to 100% RH (condensing)
Protection Degree:IP54/IP66/IP68/type 4X
Mechanical Specifications
Dimensions: Ø 110 mm
Dimensions (HxWxD), Aluminum: 109.3 x 145 x 126 mm
Dimensions (HxWxD), Stainless Steel: 107.4 x 145 x 124 mm
Weight Approx., Aluminum/Stainless Steel: 1.3/2.8 kg
Wire Size: 0.13 x 1.5 mm2/AWG 26 to 16 stranded wire
Screw Terminal Torque: 0.4 Nm
Vibration: EC 60068-2-6
2 to 25 Hz: ±1.6 mm
25 to 100 Hz: ±4 g
Display Resolution: 96 x 64 pixels
Number of Digits: 5
Backlight: Selectable ON/OFF
Backlight Color: Selectable white or red
Common Specifications
Supply
Supply Voltage, DC: Ex ia, Intrinsically Safe: 10 (12 - with backlight)...30 Vdc
Supply Voltage, DC: Other: 10 (12 - with backlight)...35 Vdc
Isolation Voltage
Isolation Voltage, Test/Working: 1.5 kVAC/50 Vac
Response Time
Response Time (Programmable): 1 to 60 s
Signal/Noise Ratio: > 60 dB
Programming:HART
Start-Up Time, Transmitter to display:Max. 5 s
Long-Term Stability, Better Than: ±0.1% of span/year
Accuracy:Better than 0.05% of selected range
Signal Dynamics, Input: 22 bit
Signal Dynamics, Output: 16 bit
EMC Immunity Influence: < ±0.1% of span
Extended EMC Immunity: NAMUR NE21, A Criterion, Burst: < ±1% of span
Input Specifications
Common Input Specifications
Max. Offset: 50% of selected max. value
RTD Input
RTD Type: Pt50/100/200/500/1000 Ni50/100/120/1000
Cable Resistance per Wire: 5 Ω (up to 50 Ω per wire is possible with reduced measurement accuracy)
Sensor Current: Nom. 0.2 mA
Linear Resistance Input
Linear Resistance Min/Max: 0 to 7000 Ω
TC Input
Thermocouple Type: B, E, J, K, L, N, R, S, T, U, W3, W5, LR
Cold Junction Compensation (CJC): Constant, internal or external via a Pt100 or Ni100 sensor
Voltage Input
Measurement Range: -800 to 800 mV
Min. Measurement Range (Span): 2.5 mV
Input Resistance:10 MΩ
Output Specifications
Current Output
Signal Range: 4 to 20 mA
Min. Signal Range: 6 mA
Load (@ Current Output): ≤ (Vsupply - 10) / 0.023 [Ω]
Load Resistance, with Backlight: ≤ (Vsupply - 12) / 0.023 [Ω]
Sensor Error Indication: Programmable 3.5 to 23 mA
NAMUR NE43 Upscale/Downscale: 23 mA/3.5 mA
Common Output Specifications
Updating Time: 440 ms
HART Protocol Revisions: HART 7 and HART 5
Observed Authority Requirements
EMC: 2014/30/EU
EAC: TR-CU 020/2011
Approvals
EU RO Mutual Recognition Type
Approval: MRA0000009
ATEX 2014/34/EU: DEKRA 15 ATEX 0058 X
IECEx: IECEx DEK 15.0039 X
FM: FM16US0009X/FM16CA0010X
CSA: 70024231
EAC Ex TR-CU 012/2011: RU C-DK.GB08.V.01316
INMETRO: DEKRA 15.0014 X
NEPSI: GYJ15.1336X, GYJ15.1337X and GYJ15.1338X
SIL: Hardware assessed for use in SIL applications
PDFs & Manuals
Show Ratings & Reviews
does Field Mounted Hart Protocol Temperature Transmitter comes without explosion proof housing?
Thank you for the inquiry. TXUN-FD includes the rated housing. Please see manual for full details and ratings.
Best regards
OMEGA