PX653
Bidirectional, Differential Low Pressure Transmitters
Models In Stock
- Clean Rooms
- HVAC
- Laboratory Fume Hoods
- NIST Traceable Calibration Certificate
PX653
From
$
750.96
Models In Stock

Product Overview
- Accuracy Class > 0.25%
- Applications Air and HVAC, Laboratories and Scientific
- Burst Pressure 20 psi Maximum
- Compensated Temperature, Max 57 °C
- Compensated Temperature, Min 2 °C
- Current Draw <5 mA
- Electrical Connection Screw Terminal
- Electrical Output Note 1 to 5 Vdc (3 wire)
- Enclosure Ratings IP62, NEMA Type 2
- Gauge Type Capacitance
- Hysteresis 0.02% FS
- Length 53 mm
- Line/Static Pressure 25 psi
- Linearity Error 0,005
- Materials, Wetted Clean, Dry, Non-corrosive Gases
- Operating Temperature, Max 72 °C
- Operating Temperature, Min -29 °C
- Pressure Type Differential
- Process Connection Note 1 ⁄4 barbed fittings (tubing TY-316-100)
- Process Connection Size 1/4 in
- Proof Pressure Up to 15 psi
- Repeatability Error 0.05% FS
- Response Time 250 ms
- Shunt Calibration Value NIST cal at 25, 50, 75 and 100% FS; upscale and downscale provided
- Supply Voltage 12 to 36 Vdc
- Thermal Effect on Zero error, Max 0.015% rdg/°F , 0.015% FS/°F
- Weight 368 g
- Width 117 mm
SPECIFICATIONS
Excitation: 12 to 36 Vdc
Output: 1 to 5 Vdc (3 wire)
Linearity: 0.3% FS (BFSL)
Hysteresis: 0.02% FS
Repeatability: 0.05% FS
Operating Temperature: -29 to 72°C (-20 to 160°F)
Compensated Temperature: 2 to 57°C (35 to 135°F)
Thermal Effects:
Zero: 0.015% FS/°F
Span: 0.015% rdg/°F
Proof Pressure: 15 psi
Burst Pressure: 20 psi
Static Pressure: 25 psi
Gage Type: Capacitance
Supply Current: <5 mA
Calibration Report: NIST cal at 25, 50, 75 and 100% FS; upscale and downscale provided
Response Time: 250 ms
Wetted Parts: Dry, clean, non-corrosive gases only
Enclosure: NEMA 2 (IP62), 107 H x 117 W x 53 mm D (4.2 x 4.6 x 2.1')
Pressure Port: ¼ barbed fittings (tubing TY-316-100)
Electrical Connections.: Screw terminal
Weight: 368 g (13 oz)
Excitation: 12 to 36 Vdc
Output: 1 to 5 Vdc (3 wire)
Linearity: 0.3% FS (BFSL)
Hysteresis: 0.02% FS
Repeatability: 0.05% FS
Operating Temperature: -29 to 72°C (-20 to 160°F)
Compensated Temperature: 2 to 57°C (35 to 135°F)
Thermal Effects:
Zero: 0.015% FS/°F
Span: 0.015% rdg/°F
Proof Pressure: 15 psi
Burst Pressure: 20 psi
Static Pressure: 25 psi
Gage Type: Capacitance
Supply Current: <5 mA
Calibration Report: NIST cal at 25, 50, 75 and 100% FS; upscale and downscale provided
Response Time: 250 ms
Wetted Parts: Dry, clean, non-corrosive gases only
Enclosure: NEMA 2 (IP62), 107 H x 117 W x 53 mm D (4.2 x 4.6 x 2.1')
Pressure Port: ¼ barbed fittings (tubing TY-316-100)
Electrical Connections.: Screw terminal
Weight: 368 g (13 oz)
Show Ratings & Reviews
Does this sensor come with a meter as shown in the picture?
Thank you for the inquire.
The meter would be a separate purchase
Date published: 2022-07-27
Are these sensors compatible with natural gas/methane?
Thank you for your inquiry, this unit is designed to work with Dry, clean, non-corrosive gases only.
If you're measuring natural gas or methane, we would recommend that you use a intrinsically safe sensor.
Date published: 2021-10-15
What does (3 wire) output mean?
This is a 3 wire voltage output device. Wiring is as follows: The positive side of the power supply is connected to the V+ terminal. Both the negative side of power supply and the negative output signal are connected to the V- terminal. The positive output signal is connected to the OUT terminal.
Date published: 2024-06-03