PX3005
Rangeable Pressure Transmitters with Display
Models In Stock
- Compact Size
- IP67 Environmental Rating
- 316SS Wetted Parts
- Scale to Display 1 of 19 Engineering Units
PX3005
From
$
779.51
Models In Stock

Product Overview
- Accuracy ± 0.2 %
- Accuracy Class 0.1% to 0.25%
- Accuracy Detail Accuracy (NLHR, 20°C ± 5°C): ± 0.2TD% SPAN
- Electrical Connection M12 4 pin Female
- Electrical Output Note 4 to 20 mA Two wire
- Operating Temperature, Max 70 °C
- Operating Temperature, Min -20 °C
- Output Signal Current
- Process Connection Size 1/4 in
- Process Connection Type NPT Male
- Process Temperature, Max 120 °C
- Process Temperature, Min -40 °C
- Storage Temperature, Max 85 °C
- Storage Temperature, Min -40 °C
The OMEGA PX3005 is a compact, rangeable, pressure transmitter ideal for monitoring pressures in process automation, hydraulic systems, compressors, pumps and in tank level applications where consistent, reliable pressure measurement is essential. The PX3005 is also ideal when measuring the difference between two high line pressures. The PX3005 utilizes proven MEMs piezoresistive pressure sensors coupled to advanced microprocessing to provide superior accuracy and performance. The rugged 316 stainless-steel enclosure is IP67 rated making it suitable for washdown environments. A 5 digit backlit LCD allows for full precision representation of process variable. Available in ranges from 1 psi to 15,000 psi, the clever transmitter module allows for configuration of the 4-20 mA signal, display of input or output, and choice of 19 measurement units. The output signal can be adjusted to re-range the transmitter or “tare” unwanted fluid head preloads. Rangeability is capable of adjusting zero and span are from -100% to 100% FS URL (Upper Range Limit) with a minimum span of 30% URL. This means a 15 psi transducer can have the zero set between -15 psi to FS 15 psi. For example, zero could be set for -15 psi and maximum 15 psi so the output would be 4 mA at -15 psi, midpoint 12 mA would be 0 psi and 20 mA would be 15 psi.
Specifications:
Turndown = nominal range of the device / set span of device
EXAMPLE: a PX3005-100GI with set span of 50psi, TD = 100psi/50psi = 2
Accuracy (NLHR, 20°C ± 5°C): ± 0.2TD% SPAN
Long Term Stability: +/- 0.1% URL / year
Ambient Temperature Effects (-20°C to 70°C): ± (0.1+0.1TD) % SPAN
Power Supply Effects:± 0.005TD% SPAN/V (Zero and Span)
Mounting Position Effects: Apply to any position. Install error less than 400Pa can be corrected by PV=0 reset.
Vibration Effects: GB/T 1827.3/IEC61298-3 tests,20g (5-2000HZ, max<± 3mm) <0.1% URL
Supply Voltage: 10.5 to 55VDC
Output Signal: 4-20mA Two wire
Sensor Response Time: 200 mS
Damping Time: Selectable, 0 to 100 S
Load Resistance Ω: <(U-10.5)/0.021
Transmission Distance: < 1000m
Power Consumption: 500mW(20.8mA output @ 24VDC)
Operating Temperature: -20 to 70°C (-4 to 160°F)
Storage Temperature: -40 to 85°C (-40 to 185°F)
Media Temperature: -40 to 120°C (-40 to 250°F)
Environmental Rating: IP67
Media: Fluids and gasses compatible with 316 SS and FKM
Process Connection/Material: 1/4"-18NPT (M) / 316 SS
Electrical Connection: 4 pin male M12
Isolating Diaphragm: 316L SS
Sensor Fill Fluid: Silicone Oil
Sensor Seal: O-ring, FKM
Housing Material: 316 SS
Weight: 0.52kg
Range Limit Table: table
table
EMC Environment:
GB/T 9254/CISPR22
GB/T 17626.2/IEC61000-4-2
GB/T 17626.3/IEC61000-4-3
GB/T 17626.8/IEC61000-4-8
GB/T 17626.4/IEC61000-4-4
GB/T 17626.5/IEC61000-4-5
GB/T 17626.6/IEC61000-4-6
Read More

Specifications:
Turndown = nominal range of the device / set span of device
EXAMPLE: a PX3005-100GI with set span of 50psi, TD = 100psi/50psi = 2
Accuracy (NLHR, 20°C ± 5°C): ± 0.2TD% SPAN
Long Term Stability: +/- 0.1% URL / year
Ambient Temperature Effects (-20°C to 70°C): ± (0.1+0.1TD) % SPAN
Power Supply Effects:± 0.005TD% SPAN/V (Zero and Span)
Mounting Position Effects: Apply to any position. Install error less than 400Pa can be corrected by PV=0 reset.
Vibration Effects: GB/T 1827.3/IEC61298-3 tests,20g (5-2000HZ, max<± 3mm) <0.1% URL
Supply Voltage: 10.5 to 55VDC
Output Signal: 4-20mA Two wire
Sensor Response Time: 200 mS
Damping Time: Selectable, 0 to 100 S
Load Resistance Ω: <(U-10.5)/0.021
Transmission Distance: < 1000m
Power Consumption: 500mW(20.8mA output @ 24VDC)
Operating Temperature: -20 to 70°C (-4 to 160°F)
Storage Temperature: -40 to 85°C (-40 to 185°F)
Media Temperature: -40 to 120°C (-40 to 250°F)
Environmental Rating: IP67
Media: Fluids and gasses compatible with 316 SS and FKM
Process Connection/Material: 1/4"-18NPT (M) / 316 SS
Electrical Connection: 4 pin male M12
Isolating Diaphragm: 316L SS
Sensor Fill Fluid: Silicone Oil
Sensor Seal: O-ring, FKM
Housing Material: 316 SS
Weight: 0.52kg
Range Limit Table: table
Gage Pressure Ranges | |||||||||
---|---|---|---|---|---|---|---|---|---|
Nominal Value | Minimum Span | Upper (URL) | Lower (URL) | Over Range Limit | |||||
kPa | PSI | kPa | PSI | kPa | PSI | kPa | PSI | kPa | PSI |
7 | 1 | 5 | 0.75 | 7 | 1 | -7 | -1 | 10.5 | 1.5 |
20 | 3 | 10 | 1.5 | 20 | 3 | -20 | -3 | 30 | 4.5 |
35 | 5 | 20 | 3 | 35 | 5 | -35 | -5 | 52.5 | 7.5 |
100 | 15 | 35 | 5 | 100 | 15 | VAC | VAC | 150 | 22 |
200 | 30 | 100 | 15 | 200 | 30 | VAC | VAC | 300 | 45 |
700 | 100 | 350 | 30 | 700 | 100 | VAC | VAC | 1050 | 150 |
MPa | PSI | MPa | PSI | MPa | PSI | MPa | PSI | MPa | PSI |
1 | 150 | 0.5 | 75 | 1 | 150 | VAC | VAC | 1.5 | 220 |
1.7 | 250 | 1 | 150 | 1.7 | 250 | VAC | VAC | 2.55 | 370 |
3.5 | 500 | 1.7 | 250 | 3.5 | 500 | VAC | VAC | 5.25 | 750 |
7 | 1000 | 3.5 | 500 | 7 | 1000 | VAC | VAC | 10.5 | 1500 |
17 | 1500 | 7 | 1000 | 17 | 1500 | VAC | VAC | 25.5 | 3700 |
35 | 3000 | 17 | 2500 | 35 | 3000 | VAC | VAC | 52.5 | 7500 |
40 | 5000 | 20 | 3000 | 40 | 5000 | VAC | VAC | 60 | 8700 |
60 | 7500 | 30 | 4500 | 60 | 7500 | VAC | VAC | 90 | 13000 |
70 | 10000 | 35 | 5000 | 70 | 10000 | VAC | VAC | 105 | 15000 |
100 | 15000 | 50 | 7250 | 100 | 15000 | VAC | VAC | 150 | 21750 |
Absolute Pressure Ranges | |||||||||
---|---|---|---|---|---|---|---|---|---|
Nominal Value | Minimum Span | Upper (URL) | Lower (URL) | Over Range Limit | |||||
kPa | PSIA | kPa | PSIA | kPa | PSIA | kPa | PSIA | kPa | PSIA |
35 | 5 | 10 | 1.5 | 35 | 5 | 0 | 0 | 50 | 7.5 |
100 | 15 | 35 | 5 | 100 | 15 | 0 | 0 | 150 | 22 |
200 | 30 | 100 | 15 | 200 | 30 | 0 | 0 | 300 | 45 |
700 | 100 | 350 | 50 | 700 | 100 | 0 | 0 | 1050 | 150 |
MPa | PSIA | MPa | PSIA | MPa | PSIA | MPa | PSIA | MPa | PSIA |
1 | 150 | 0.5 | 75 | 1 | 150 | 0 | 0 | 1.5 | 220 |
1.7 | 250 | 1 | 150 | 1.7 | 250 | 0 | 0 | 2.55 | 370 |
3.5 | 500 | 1.7 | 250 | 3.5 | 500 | 0 | 0 | 5.25 | 750 |
GB/T 9254/CISPR22
GB/T 17626.2/IEC61000-4-2
GB/T 17626.3/IEC61000-4-3
GB/T 17626.8/IEC61000-4-8
GB/T 17626.4/IEC61000-4-4
GB/T 17626.5/IEC61000-4-5
GB/T 17626.6/IEC61000-4-6