Welcome to our new website, found an issue or bug? Please report it here

SSRDIN600
Single- and Three-Phase DIN Rail Mount Solid State Relays
Models In Stock
- Ratings Up to 30 A (22.5 mm), 45 A (45 mm), or 25 A 3-Phase
- LED Input Status Indicator
- Integral Heat Sink Eliminates the Need for Complex Thermal Calculations
- DBC Substrate for Superior Thermal Performance
SSRDIN600
From
$
95.49
Models In Stock

Product Overview
- Current, Min 100 mArms
- Enclosure Ratings IP20
- Frequency 40 to 63 Hz
- Housing Material UL 940VD (self-extinguishing)
- Input/Output-to-Ground Isolation 4000 Vrms
- Input Resistance Current Regulated
- Input-to-Output Capacitance 8 pF
- Isolated Analog Voltage 4000 Vrms
- Signal fail-safe 500 Vµs
- Storage Temperature, Max 100 °C
- Storage Temperature, Min -40 °C
- Weight 600 g
Designed for superior thermal performance in harsh industrial environments, OMEGA’s new SSRDIN/SSR3PH relay is the most advanced DIN rail solid state relay in its range. The epoxy-free design eliminates stress on internal components, preventing damage to the encapsulant during load failure. The vertical placement of the directbond substrate allows the SCR die to efficiently transfer heat to the heat sink and into ambient air. As a result, these relays can operate at a lower temperature than their competitors, which accounts for the higher I2T and surge-current ratings.
The SSRDIN’s internal transient protection is fully repeatable, making MOVs or other external suppressors unnecessary. This feature allows the output to conduct load-current when a transient is detected across the output terminals, rather than forcing load-current through the protection circuit. Thus, no degradation of protection occurs.
These relays are ideal for numerous commercial and industrial applications, including mercury relay replacement, professional food-service equipment (ovens, fryers, dispensing equipment, conveyors, etc.), sterilizers, temperature control systems, plastic extrusion/thermoforming machinery, HVAC and R, kilns, packaging equipment, sorting equipment, wave solder and reflow systems, lighting systems, pump controls, incubators, motor-switching, and UPS systems.
SPECIFICATIONS
Operating Temperature: -20 to 80ºC* (-4 to 176°F)
Storage Temperature: -40 to 100 ºC (-40 to 212°F)
Input-to-Output Isolation: 4000 Vrms
Input/Output-to-Ground Isolation: 4000 Vrms
Input-to-Output Capacitance: 8 pF (typical)
Operating Frequency: 40 to 63 Hz
Housing Material: UL 940VD (self-extinguishing)
Weight: 600 g (1.3 lb)
* For 108 to 280 Vac input.
The SSRDIN’s internal transient protection is fully repeatable, making MOVs or other external suppressors unnecessary. This feature allows the output to conduct load-current when a transient is detected across the output terminals, rather than forcing load-current through the protection circuit. Thus, no degradation of protection occurs.
These relays are ideal for numerous commercial and industrial applications, including mercury relay replacement, professional food-service equipment (ovens, fryers, dispensing equipment, conveyors, etc.), sterilizers, temperature control systems, plastic extrusion/thermoforming machinery, HVAC and R, kilns, packaging equipment, sorting equipment, wave solder and reflow systems, lighting systems, pump controls, incubators, motor-switching, and UPS systems.
SPECIFICATIONS
Operating Temperature: -20 to 80ºC* (-4 to 176°F)
Storage Temperature: -40 to 100 ºC (-40 to 212°F)
Input-to-Output Isolation: 4000 Vrms
Input/Output-to-Ground Isolation: 4000 Vrms
Input-to-Output Capacitance: 8 pF (typical)
Operating Frequency: 40 to 63 Hz
Housing Material: UL 940VD (self-extinguishing)
Weight: 600 g (1.3 lb)
* For 108 to 280 Vac input.
Show Ratings & Reviews
Can i use SSR3PH600DC25 this part on 210vac coil supply?
Hi Shreyas,
Thanks again. Yes you can use this SSR output to drive an AC coil in an On/Off control application.
Best regards
OMEGA
Date published: 2021-04-30
Hi, I have the CNI16D33-C4EIT part, we have SSR with 24vdc coil control, can i connect 24vdc to the output?
Hi Shreyas,
Thank you for the inquiry. Yes you can use the relay contacts on this controller for your 24 VDC coil.
Best regards
OMEGA
Date published: 2021-04-30