Skip to search Skip to main content Skip to navigation

Welcome to our new website, found an issue or bug? Please report it here

We noticed you are from . Visit your local site for regional offers and live support.

CT5100

1 or 2 Channel, 10" Circular Chart Recorders

C$2,979.31

Item# CT5100

Volume discounts available
Volume Discount Schedule
Quantity Price each
1-4 C$2,979.31
5-9 C$2,830.34
10-24 C$2,770.76
25-49 C$2,651.59
50-99 C$2,592.00
100+ C$2,532.41

In Stock

Lead Time (If not in stock): 16 weeks

Product Specs

<< See all Product Models
Brand
Accuracy ± 0.5 %
Accuracy Note Chart Recording: 0.5% of chart span reference accuracy, Chart Rotation: ±0.5% of rotation time, assuming all backlash removed, Chart Rotation: ±0.5%, Chart Speed: ±1%
Approvals UL, FM
Approvals Note Safety: UL Approved for USA:UL 1092, UL 916 and QUXY, pending UL Certified for Canada:CSA Spec 142, pending Limit/Device: FM, pending
CMRR >120 dB @ 50/60 Hz, 260 Vac max
Chart Diameter 254 mm
Chart Note Chart Span: Bottom and top of span, -9999 to 9999 units; Chart Drive: DC Stepper Motor; Chart Drive: Stepper Motor
Chart Speed 8 Hours to 7 Days
Cold Junction Compensation 0.04°/°C deviation from 25°C
Conduit Entrance 3 Openings on the Right Side
Current Measurement Range 0 to 20 mA
Cutout Dimensions 322.58 x 322.58 mm
Data protection EEPROM Storage
Display Note 4-digit, 14 mm H (0.56"), red, 7-segment, LED display, Display Modes: Normal: process value(s) or blank Keypad: 3 keys for programming and unit operation
Display Type LED
Enclosure Ratings IP54, NEMA Type 3
Height 355.6 mm
Impedance Input >100 MΩ for T/C and mV inputs, 100 kΩ for 5 V inputs, 4.7 Ω for µA inputs
Input Note Input Correction: Offset adjustment: 999 to 999 units;Input Isolation: 350 Vac, 500 Vdc
LED Indicators 5 Red LED Alarm Status Indicators, 1 green LED pen 2 indicator
Length 96.5 mm
Material Construction Option Standard
Materials Noryl, Acrylic
Measurement Range Note Thermocouple: J: 0 to 760°C, K: 0 to 1360°C, T: -200 to 400°C, R: 200 to 1650°C, S: 200 to 1650°C RTD: -140 to 400°C Current: 0 to 20 mA, 4 to 20 mA Voltage: 0 to 25 mV, 0 to 50 mV, 10 to 50 mV, 0 to 5 V, 1 to 5 V
Measurement Type Thermocouple, RTD, Current, Voltage
Mounting Panel Mount or Wall Mounting
NMRR 85 db @ 60 Hz or greater
Number of Channels 1
Number of Relays N/A
Operating Environment Reference Operating Condition: 25 °C
Operating Temperature, Max 50 °C
Operating Temperature, Min 0 °C
Panel Depth 64 mm
Panel Protrusion 33 mm
Pen Type Disposable Fiber tip
Power Consumption 18 VA
RTD Type 100 Ω Pt sensor; α= 0.00385
Recording Color Pen 1: Red
Relative Humidity 10 to 90% RH, non-condensing
Sampling Rate 1 Scan per second for Non-RTD inputs; 1 Scan per 1.2 seconds for RTD inputs
Sensor Break Detection Sensor Fault Detection: Display goes to “SnSr” and pen goes up-scale if a sensor break is detected. No sensor break can be detected for zero-based volt and milliamp ranges. Display goes to “Hi” 10% above span; display goes to “Lo” 10% below span or zero, whichever is higher.
Sensor Input Configuration 150 µA
Standard Limits of Error Error Limit: Cold-Junction Compensation Error: ±0.2°C @ 25°C, Linearization Error: T/Cs: ±0.25°C typical, ±0.5°C worst case , RTDs: ±0.1°C typical, ±0.3°C worst case, Ambient Temperature Error: ±0.01% of span per °C deviation from 25°C; Measurement Error: Type J, K, T, R, S and RTD: ±0.25% of span ±1 degree; mA, mV and Vdc: ±0.25% of scaled span plus 1 leastsignificant digit
Storage Temperature, Max 65 °C
Storage Temperature, Min -40 °C
Supply Power Note Line Voltage: 90/264 Vac, 50/60 Hz; optional: 20 to 50 Vac, 50/60 Hz, or 22 to 65 Vdc
Supply Power Type AC
Supply Voltage 90 to 264 Vac
Switch Rating 5 A @ 115 Vac
Switch Rating Note Relays: SPDT; contacts rated 5 A resistive @ 115 Vac,2.5 A resistive @ 230 Vac, 1⁄8 hp @ 230 Vac (single phase),250 VA @ 115/230 Vac
Switch Type SPDT NO/NC, Selectable
Temperature Measurement Range J: 0 to 760°C, K: 0 to 1360°C, T: -200 to 400°C, R: 200 to 1650°C, S: 200 to 1650°C, RTD: -140 to 400°C
Thermocouple Type J, K, T, R, S
Voltage Measurement Range 0 to 25 mV, 0 to 50 mV, 10 to 50 mV, 0 to 5 V, 1 to 5 V
Weight 8.8 kg
Width 355.6 mm
Wire Code Option 2- or 3- Wire
See All Specs Show Less
1 or 2 Channel, 10" Circular Chart Recorders CT5100 CT5100
Rated 4 out of 5 by from USER FRIENDLY WE HAVE HAD THESE FOR A FEW YEARS . TWELVE OF THEM THROUGH OUT THE PLANT THEY HAVE WARE AND TEAR, SO WE NEED A PART BREAK DOWN AND SERVICE MANUEL .I AM TOLD THEY IS NONE. WHY?
Date published: 2017-07-31
  • y_2025, m_2, d_22, h_8
  • bvseo_bulk, prod_bvrr, vn_bulk_3.0.42
  • cp_1, bvpage1
  • co_hasreviews, tv_0, tr_1
  • loc_en_CA, sid_CT5100, prod, sort_[SortEntry(order=HELPFULNESS, direction=DESCENDING), SortEntry(order=POSITIVE_FEEDBACK, direction=DESCENDING), SortEntry(order=SUBMISSION_TIME, direction=DESCENDING)]
  • clientName_omega
  • bvseo_sdk, java_sdk, bvseo-4.0.0
  • CLOUD, getReviews, 4ms
  • REVIEWS, PRODUCT
en-CA
en_CA
Save Configuration