Series-CDTR
CO2, RH & Temp Transmitters for Efficient Building Management Systems
- Digital Intelligence Temperature Compensation Algorithm (DITCA¢) eliminates errordue to the self heating effects of wall mount combination devices
- Single beam dual wavelength NDIR CO2 sensor
- Replaceable humidity/temperature sensors
- Physical hardware lockout
- Service display tool available for duct mount and wall mount units without an LCD
- Relay output option
Series-CDTR
From
C$
0.00

Can't find the right model?
Use our custom configurator to fine tune your product
Product Overview
- Applications Building and Maintenance, HVAC
- Carbon Dioxide Concentration, Max 2000 ppm
- Carbon Dioxide Concentration, Min 0 ppm
- Carbon Dioxide Response Time 120 s (τ90)
- Compliance CE
- Electrical Output 4 to 20 mA
- Operating Temperature, Max 122 °F
- Operating Temperature, Min 32 °F
- Output Detail CO2 Output: 4-20 mA / 0 to (5 or 10) VDC; RH Output: 4-20 mA / 0 to (5 or 10) VDC
- Output Signal Current, Voltage
- Power Consumption Average: 2 W; Peak: 3.75 W
- Relative Humidity 0 to 85% RH Non-Condensing
- Relative Humidity Accuracy ± 2% RH
- Relative Humidity Input Range 10 to 90% RH
- Sensor Life 15 Years
- Supply Power Type AC/DC
- Supply Voltage 19 to 28 Vac/16 to 35 Vdc
- Switch Type N/A
- Voltage Output Range 0 to 5 Vdc, 0 to 10 Vdc
The Series CDTR Carbon Dioxide, Relative Humidity and Temperature Transmitters reduce the number of sensors mounted on a wall or in a duct. By combining CO2, RH, and temperature in one device, system integrators are able to reduce installation time while lowering material cost at the same time. Like our popular Series CDT Carbon Dioxide Transmitter, a single beam dual wavelength non-dispersive infrared (NDIR) sensor is used to automatically correct the measurement in both occupied* and unoccupied buildings against light source aging effects. In order to achieve the best possible accuracy, the Series CDTR also includes digital barometric pressure adjustment and the ability to field calibrate the sensor. Universal outputs for both carbon dioxide and relative humidity allow users to select the transmitter output to be 4 to 20 mA, 0 to 5 VDC, or 0 to 10 VDC to work with virtually any building management controller. Additionally, passive thermistor or RTD sensor can be ordered for a temperature output. For applications that require visual indication, the wall mount configurations of the Series CDTR can be ordered with an integral LCD display. The display can be configured to display temperature only, relative humidity only, CO2 only, CO2 and humidity, or CO2 and temperature. Push buttons are standard on all configurations of the transmitters for access to the menu structure. To prevent tampering, the action of the buttons can be locked out using an internal jumper selection.
*For buildings occupied 24 hours per day, it is recommended that calibration be verified every 6 to 12 months depending on application.
For models with resistive thermistors or RTD outputs, please click here for temperature to resistance lookup tables.
Product Applications
- Demand control ventilation in schools, office buildings, hospitals, and other indoor environments
- LEED® certification
Show Ratings & Reviews
CDT - AQ-CDT Duct Mount Manual (Pre April 2022) - AQ_CDT_CDTR_2_pdf user manual
CDT - AQ-CDT Duct Mount Manual (Post April 2022) - AQ_CDT_CDTR_3_pdf user manual
CDT - AQ-CDT-N Wall Mount Manual (Pre April 2022) - AQ_CDT_CDTR_E_N_2_pdf user manual
CDT - AQ-CDT-N Wall Mount Manual (Post April 2022) - AQ_CDT_CDTR_E_N_3_1_pdf user manual