Welcome to our new website, found an issue or bug? Please report it here

TX13-Smart-Temp-Tx
Thermocouple Input Temperature Transmitter w/ Pushbutton Config
Models In Stock
TX13-Smart-Temp-Tx
From
C$
188.46
Models In Stock

Product Overview
- Accuracy ± 5 µA
- Accuracy Note (mA output/2000) or 5 uA (whichever is the greater)
- Approvals BS EN 61326 ; 1998 – Electrical equipment for measurement and control ANNEX A ; ANNEX F
- Calibration Pushbutton
- Cold Junction Compensation ±0.05°C/°C
- Cold Junction Temperature Accuracy ±0.5 °C
- Diameter 43 mm
- Electrical Connection Screw Terminal
- Electrical Output 4 to 20 mA
- Height 21 mm
- Humidity Range 10 to 90% RH non condensing
- Input Accuracy ± 0.5 °C
- Operating Temperature, Max 85 °C
- Operating Temperature, Min -40 °C
- Output Load [(Vsupply-10)/20] kΩ
- Probe Length 0 mm
- Programmable Functions offset, Range, Sensor Burnout Indication, sensor type
- Response Time 1 sec
- Self Heating Effect 0.2 uA/V
- Sensor Type Transmitter
- Setup Controls Pushbutton, Program LED will flash in bursts
- Sheath Material N/A
- Stability Offset: 0.1°C/°C;Span: 0.05°C/°C
- Start Up Time I out < 4 mA during start up
- Storage Temperature, Max 90 °C
- Storage Temperature, Min -50 °C
- Supply Power Type DC
- Supply Voltage 10 to 30 Vdc
- Temperature Input Range K: -200 to 1370 °C; J: -100 to 1200 °C; E: -100 to 1000 °C; N: -180 to 1300 °C; T: -100 to 400 °C; R -10 to 1760 °C; S: -10 to 1760 °C
- Thermal Effects 1 uA/°C
- Update Rate, Max 500 ms
- Warm Up Time 1 min to full accuracy
- Weight 31 g
The TX13 in-head mounting thermocouple transmitter converts a thermocouple input over a configured range to a standard industrial (4 to 20 mA) transmission signal. A simple push button operation allows the user to select thermocouple type, burnout direction, select fixed ranges and trim 4 and 20 mA points. The in-head transmitter incorporates the latest digital technology to ensure accurate drift-free performance.
The default factory scaling is for a range of 0 to 1000°C and Type K thermocouple input, with up-scale burnout.
Specifications
The default factory scaling is for a range of 0 to 1000°C and Type K thermocouple input, with up-scale burnout.
Specifications
PDFs & Manuals
Show Ratings & Reviews
Rated 5 out of
5
by
carbonell from
Great buy
Excellent device for tight applications. I put it inside a 3" junction box and fit perfectly.
Date published: 2016-02-15
Rated 3 out of
5
by
scoob from
Beginner
I like the transmitter that you guys have, as it's very versatile. I am new to the field and I'm teaching myself setup and calibration. I thought that it would have been nice to know that I would have to expect to do that in advance and with more direction. The device certainly needed trimmed to the (-100C / 100C) range of the T type thermocouple. I thought that it would be a lot closer to the 4mA & 20mA output than it was. I had to buy a calibrator and learned how to operate the new machine and was able to trim that device to exactly (-100C / 100C) to 4mA & 20mA, and that was fun, and the device was easy to configure. It was so far off though it surprised me, it seems the true zero and span for the T type was actually set to something other than (-100C / 100C) so it's not plug and play, and maybe they never are. I'm a beginner, and now maybe a novice! What I've learned I will be able to apply to many things in our facility and I certainly like the easy configuration that your product offers, now that I know how it all works. The Best School is the School of Hard Knocks!
Date published: 2016-03-18
Rated 5 out of
5
by
Logan134 from
TX13
Easy Integration. No problems calibrating the sensor either
Date published: 2025-01-29
Rated 5 out of
5
by
Logan134 from
Smart Temperature Transmitters Review
Came in very timely manner, Will be used in a chemical environment
Date published: 2024-06-10
What is the country of origin for your TX13 transmitters?
Thank you for the inquiry. TX13 origin is Great Britain.
Best regards
OMEGA
Date published: 2024-03-27
Could you please share reliability data (FIT/MTBF) for the TX13-TX-SCALED? Thank you
Hi RM2021,
Thank you for the inquiry. Unfortunately we do not offer requested data on the requested product.
Best regards
OMEGA
Date published: 2021-10-27
To use with Omega SA2C-K, type K TC with -50 to 200C range: -50 to to 200 is not one of the preconfigured ranges for TX13. What is the PN to order if we want the transmitter come with -50 to 200 reconfiguration?
Thank you for the inquiry. You can add factory configuration option to a new TX13 with part# TX13-TX-SCALED. When placing order add scaling detail to description on PO copy. Else, if placing order via web site, add scaling details to Special Instructions box in line item details in shopping cart.
Best regards
OMEGA
Date published: 2023-08-13
Can you use any type of TC on this TX? ex. J or T if it only states K on the device?
Thank you for your inquiry NCJOe. TX13 is compatible with K, J, N, E, T, R, S Thermocouples.
Date published: 2022-08-10