Series-V7

Flotect® Flow Switch for Liquids, NEMA 4X, Ideal for Boilers & Pumps

  • Superior performance with magnetically-actuated switching design
  • Increased product life due to free-swinging vane, which attracts a magnet within the solid metal switch body to actuate a snap switch by means of a simple lever arm with no bellows, springs, or seals to fail
  • Meets application requirements with durable leak proof body machined from bar stock
  • Long operating life with robust vane design which is rigid and field trimmable for set point adjustment
Series-V7
From C$ 0.00
Flotect® Flow Switch for Liquids, NEMA 4X, Ideal for Boilers & Pumps Series-V7 Series-V7
loading all models

Can't find the right model?

Use our custom configurator to fine tune your product

Product Overview
  • Compliance CE, UL
  • Electrical Connection 1/2 in NPS female Conduit with Screw Terminal block
  • Enclosure Ratings IP66, NEMA Type 4X, Weatherproof
  • Materials Aluminum
  • Media Compatibility Alcohols, Compatible Liquids, Oils, Water
  • Mounting Orientation Horizontal, Vertical
  • Operating Temperature, Max 250 °F
  • Operating Temperature, Min -40 °F
  • Pipe Size, Max 4 in
  • Pipe Size, Min 1 in
  • Pressure Type Gauge
  • Process Connection Size 1 in
  • Proof Pressure Up to 250 psi
  • Sensor Material Stainless Steel, Brass, Ceramic
  • Set Point Adjustment Vane adjustments
  • Switch Rating 10 A @ 125, 250, 480 Vac; 1/8 hp @ 125 Vac, 1/4 hp @ 250 Vac
  • Switch Type SPDT Snap
  • Weight 500 g

The Series V7 Flotect® Flow Switch is an inexpensive range switch for use with compatible liquids to start or stop electronic operated equipment when flow or no-flow conditions occur. Design is standard weatherproof, meeting NEMA 4X.

California Residents:  Click Here for Proposition 65 WARNING.

Product Applications

  • Proof of boiler flow
  • Shuts down burner when air flow through heating coil fails
  • Protects pumps, motors and other equipment against low or no flow
  • Stops liquid cooled engines, machines and processing when coolant flow is interrupted
  • bvseo_sdk, java_sdk, bvseo-4.0.0
  • CLOUD, getReviews, 4ms
  • REVIEWS, PRODUCT
  • bvseo-msg: The resource to the URL or file is currently unavailable.;
  • bvseo_sdk, java_sdk, bvseo-4.0.0
  • CLOUD, getContent, 19ms
  • QUESTIONS, PRODUCT
  • bvseo-msg: The resource to the URL or file is currently unavailable.;
en-CA
en_CA
Save Configuration