Bienvenue sur notre nouveau site Web, vous avez rencontré un problème ou un bug? Veuillez le signaler ici

R-Series
DIN Rail Mount Circuit Breakers, 17.5 mm (0.69 in) Width per Pole
Modèles en stock
- DIN Rail Mounted
- 17.5 mm (0.69') Width per Pole
- Thermal Magnetic Overcurrent Protection
- 0.5 - 60 A, 480Y/277 Vac, 50/60 Hz
R-Series
Depuis
C$
33.59
Modèles en stock

L'aperçu du produit
- Applications Energy Generation and Distribution
- Calibration Temperature 30 K
- Color Options Black
- Current Type AC
- Electrical Life 10,000 cycles on/off
- Enclosure Ratings IP20
- Frequency 50/60 Hz
- Mechanical Life >6,000 cycles
- Operating Temperature, Max 55 °C
- Storage Temperature, Max 70 °C
- Storage Temperature, Min -40 °C
- Tightening Torque 17.7 to 25 lb-in
- Vibration Resistance >15 g (18 to 50 Hz)
- Voltage Rating 480Y/277 Vac
- Wire Gauge N/A
Description
While UL489 branch circuit breakers protect feeder or branch circuits, R Series UL1077 supplementary protectors are made to trip faster than a standard UL489 circuit breaker, therefore providing additional protection for specific devices. Supplementary protectors provide critical protection in applications where branch circuit protection is not required, or is already provided by a separate device.R Series supplementary protectors are available in one, two, and three-pole configurations and up to 20 different current ratings from 0.5A to 60A and can safely be used in applications up to 480Y/277 Vac with a 10 kA short circuit withstand Rating.
Three different trip characteristics, including B, C and D curves, give you the ability to configure the exact protection scheme you require.
B-Trip Protectors
Include business equipment, wiring protection, lighting, appliances, control circuits and some electronic applications. Relatively long thermal trip delay but low magnetic trip point.
C-Trip Protectors
Include lighting, wiring protection, appliances, business equipment, and control circuit applications. Relatively long thermal trip delay and medium magnetic trip point.
D-Trip Protectors
Include control transformers, power supplies and reactive loads. Relatively long thermal trip delay and very high magnetic trip point.
Features Provided by the Different Types of Circuit Breakers
UL1077 Recognized Supplementry Protectors
Overload Protection
UL508 Listed Manual Motor Controllers
Overload Protection
Switching Function
Disconnect Function
UL489 Miniature Molded Case Circuit Breakers
Overload Protection
Switching Function
Disconnect Function
Short Circuit Protection
Specifications
Voltage Rating: 480Y/277 Vac
Short Circuit Withstand Rating (UL - Ratings):
0.5-10A (RC): 10kA with no back-up fuse
12-60A (RC): 10kA with UL-listed Class J back-up fuse 5kA with no back-up fuse
Calibration Temperature: 30°C (86°F)
Operating Temperature: -25 to 55°C (-13 to 131°F)
Storage Temperature: -40 to 70°C (-40 to 158°F)
Terminal Size Acceptability:
Top: 18-3 AWG
Bottom: 18-2 AWG (line/load reversible)
Tightening Torque (min/max): 17.7/25 lb-in. (2/2.8 Nm)
Terminal Protection Degree: IP20
Vibration Resistance: ≠¥15g
Dimensions:
Height: 89.3 mm (3.51")
Width:
One Pole: 17.5 mm (0.69")
2 Pole: 35 mm (1.38")
3 Pole: 52.5 mm (2.07")
Depth:68.4 mm (2.69") from DIN rail
Use the "Part Number Builder" below for product selection.
Afficher les notes et les avis
RoHS 2015/863 - Voir le certificat
Approuvé CE
Composant certifié UL et cULus