Bienvenue sur notre nouveau site Web, vous avez rencontré un problème ou un bug? Veuillez le signaler ici

ITHX-D3-Series
DIN Rail Mount Temperature and Humidity Virtual Chart Recorder
- Web Server
- Alarms by Email or Text Message
- Accurate Readings
- Data Logging
ITHX-D3-Series
Depuis
C$
630.00

L'aperçu du produit
- Accuracy Note Temperature: ± 0.5°C for 5 to 45°C; up to ± 1.5°C for -40 to 5°C and 45 to 124°C, Accuracy/Range at 25°C: Non-Condensing: 10 to 90%: 2.75% RH, 5 to 10% and 90 to 95%: ± 3%, 0 to 5% and 95 to 100%: ± 4%
- Approvals CE, FCC-B
- Cable Temperature, Max 125 °C
- Cable Temperature, Min -40 °C
- Configuration Internal Web UI
- Data Interface Ethernet
- Data Interface Note Ethernet : (RJ45) Fixed or auto negotiating 10/100BASE-T, AUTO MDI/MDIX Supported Protocols:TCP, UDP, SNMP, SMTP, NTP, ARP, ICMP, DHCP, DNS, HTTP, and Telnet
- Electrical Connection Stripped Leads
- Form factor DIN rail mount
- Height 0.99 in
- Hysteresis ± 1% RH
- Input Type External
- Length 3.54 in
- Logging Modes Fixed interval
- Measurement Type Relative Humidity, Temperature
- Non-Linearity ± 3%
- Operating Temperature, Max 85 °C
- Operating Temperature, Min -40 °C
- Probe Diameter 0.63 in
- Probe Length 5 in
- Probe Style Industrial Probe
- Relative Humidity Accuracy ± 1.5 °C
- Repeatability ± 0.1%
- Response Time Temperature: 5 to 30 sec, RH: 8 sec
- Response Time Note Temperature: 5 to 30 seconds, tau 63%, RH: 8 seconds, tau 63%
- RH Measurement Range 0 to 100% RH
- Sensor Type Screw Terminal
- Software OPC Server; macro for data logging in Excel program; compatible with Windows® operating systems
- Storage Temperature, Max 125 °C
- Storage Temperature, Min -40 °C
- Supply Power Note 10 to 32 Vdc switching power supply (sold separately)
- Supply Power Type DC
- Supply Voltage 10 to 32 Vdc
- Temperature Accuracy ± 0.5 °C
- Temperature Measurement, Max 124 °C
- Temperature Measurement, Min -40 °C
- Temperature Repeatability ± 0.1 °C
- Weight 0.68 lb
- Width 4.53 in
View Temperature and Humidity with a Web Browser
The OMEGA™ iTHX transmitter lets you monitor and record temperature, relative humidity, and dew point over an Ethernet network or the Internet with no special software except a web browser. The iTHX serves active web pages to display realtime readings, charts of temperature and humidity, or log data in standard data formats for use in a spreadsheet or data acquisition program such as Excel or Visual Basic.
The virtual chart viewed on the web page is a JAVA™ Applet that records a chart over the LAN or Internet in real time. With the iTHX, there is no need to invest time and money learning a proprietary software program to log or chart the data.
Email Alarms
All iTHX models that are on a LAN that is connected to the Internet can trigger an alarm that can be sent by email to a user or a distribution list anywhere in the world, including text messages to cell phones and PDA’s.
Typical Applications
The iTHX is great for monitoring temperature and humidity in applications such as: clean rooms, computer rooms, HVAC systems, pharmaceutical and food processing and storage, hospitals, laboratories, semiconductor labs, electronic assembly, warehousing, museums, manufacturing, greenhouses and, farm animal shelters.
The OMEGA™ iTHX transmitter lets you monitor and record temperature, relative humidity, and dew point over an Ethernet network or the Internet with no special software except a web browser. The iTHX serves active web pages to display realtime readings, charts of temperature and humidity, or log data in standard data formats for use in a spreadsheet or data acquisition program such as Excel or Visual Basic.
The virtual chart viewed on the web page is a JAVA™ Applet that records a chart over the LAN or Internet in real time. With the iTHX, there is no need to invest time and money learning a proprietary software program to log or chart the data.
Email Alarms
All iTHX models that are on a LAN that is connected to the Internet can trigger an alarm that can be sent by email to a user or a distribution list anywhere in the world, including text messages to cell phones and PDA’s.
Typical Applications
The iTHX is great for monitoring temperature and humidity in applications such as: clean rooms, computer rooms, HVAC systems, pharmaceutical and food processing and storage, hospitals, laboratories, semiconductor labs, electronic assembly, warehousing, museums, manufacturing, greenhouses and, farm animal shelters.
PDF et manuels
Logiciels et pilotes
Afficher les notes et les avis
The manual mentions switching capabilities but I don't really see any other information on that. Upon reaching a certain temperature or humidity is there an electrical output that can be used to trigger an alarm or a control device?
Thank you for your interest in our Product. Please email your question to the Data Acquisition Department … das@omega.com for review. They will get back you