Horloge à 6 bases de temps, 48x48mm (1/16 DIN)PTC-1A-seriesPTC-1A-series
L'aperçu du produit
Accuracy
± 20 ms or ± 0.5 % of set time
Contact Rating
SPDT relay, rated 7 A at 30 Vdc/240 Vac resistive
Cutout Dimensions
45 x 45 mm
Display Type
3 Digit Display
Electrical Life
200,000 operations at rated load
Form factor
1/16 DIN
Frequency
47 to 440 Hz
Height
48 mm
Isolation
1500 Vac 50 Hz
Length
89 mm
Mechanical Life
10 million operations
Number of Relays
1
Operating Temperature, Max
50 °C
Operating Temperature, Min
0 °C
Power Consumption
1 W
Reset
10 ms
Storage Temperature, Max
85 °C
Storage Temperature, Min
-20 °C
Supply Power Type
AC/DC
Timer Range
0.1 to 9.99 sec, 0.1 to 99.9 sec, 0.01 to 9.99 min, 0.1 to 99.9 min, 0.01 to 9.99 hrs, 0.1 to 9.99 hrs
Width
48 mm
Description
L'horloge PTC-1A est un module de commande facile à configurer et à mettre en oeuvre dans un environnement industriel. Le PTC-1A est particulièrement adapté pour le contrôle de systèmes nécessitant à la fois une commande au temps et en température tels que les fours de vieillissement, l'impression à chaud et la mise en étanchéité d'enceintes..
Le commutateur monostable PTC-SW du PTC-1A permet de commander à distance le redémarrage des cycles. Pour obtenir les caractéristiques complètes de ces produits, consultez la notice commerciale par le lien en bas de cette page.
Rated 3 out of
5 by
ControlFreq from
Easy To Use Pay Attention To ReviewThis was easy to setup, but there are a few challenges. Do not use this in conjunction with an LED indicator. An LED indicator will cause the trigger circuit to instantly trigger, prior to the trigger input. Also when updating the time, the new programmed time will not display until either the completion of the next timing event, or a power cycle. When using in a panel mount application, I recommend wrapping the plastic clips with TyWraps to keep the latches tight against the relay. The PTC-1A shipped with the relay, the octal base with terminal points/screws, and the panel mount hardware. This is everything required to mount to a Panel face, or a backplane by screwing the base down.
what is the ptc-sw switch? The product manual from 1978 doesn't mention it.
Asked by: aromat666
Thank you for your inquiry. The use of the PTC-SW momentary switch, included with the PTC-1A, allows cycle reset from a remote location for the PTC-1A.
Answered by: Application Engineer CB
Date published: 2022-09-01
What is the relay amp rating?
Asked by: JParnell
Thank you for your inquiry. The Single-Pole Double-Throw Relay is rated 10A @ 30VDC/240VAC resistive load only. Limited to 7A if used with socket.