MSX Magnesense® Differential Pressure Transmitter, 32 Ranges, Dual Output

Modèles en stock
  • Read LCD values easier with rotatable 180° display
  • Quick and easy wiring via the optional toolless terminal block
  • Add safety to variety of applications with UL94 V-0 and plenum ratings
Series-MSX-Magnesense
Depuis C$ 178.86
Modèles en stock
MSX Magnesense® Differential Pressure Transmitter, 32 Ranges, Dual Output Series-MSX-Magnesense Series-MSX-Magnesense
loading all models

Vous ne trouvez pas le bon modèle ?

Utilisez notre configurateur personnalisé pour affiner votre produit

L'aperçu du produit
  • Accuracy Detail ± 1% FSO
  • Applications Building and Maintenance, HVAC
  • Burst Pressure 6 psi Maximum
  • Compliance CE
  • Electrical Connection 1/2 NPS female Conduit with Screw Terminal block
  • Electrical Output 4 to 20 mA, 0 to 5 Vdc, 0 to 10 Vdc
  • Enclosure Ratings IP66, NEMA Type 4X, UL94 V-0, UL 2043 (Plenum)
  • Long Term Stability ± 1% FSO/year
  • Loop Resistance Current Output: 0 to 1250 Ω max, Voltage Output: Load resistance 1 kΩ min.
  • Material Construction Option N/A
  • Materials, Wetted Consult Factory
  • Media Compatibility Air, Argon, Carbon dioxide, Helium, Nitrogen, Non-Conductive Gases, Non-Corrosive Dry Gases
  • Mounting Note Not Position Sensitive
  • Number of Wires 2, 3
  • Operating Temperature, Max 70 °C
  • Operating Temperature, Min -20 °C
  • Output Detail Field Selectable
  • Output Signal Current, Voltage
  • Power Consumption max 21 mA
  • Pressure Type Differential
  • Process Connection Size 1/8 in, 3/16 in, 1/4 in
  • Process Connection Type Stepped Barb Fitting
  • Response Time 3 s
  • Response Time Note Instantaneous (default) or 3 s (selectable)
  • Span Adjustment Push Button
  • Supply Power Type AC/DC
  • Supply Voltage 2-Wire: 10 to 36 Vdc, 3-Wire: 17 to 36 Vdc/21.6 to 33 Vac
  • Weight 230 g
  • Wire Gauge 26 to 16 AWG
  • Zero Setting Adjustable Range Digital push-button

The Series MSX Magnesense® Differential Pressure Transmitter combines the stability and versatility of the original Series MS2 Magnesense® II transmitter for use in building control applications. The MSX simplifies the ordering process to deliver the desired configuration, which reduces product setup time. Pressure ranges are available in Pa, mm w.c., and in w.c. All pressure ranges can be configured in unidirectional or bidirectional modes, providing a total of 32 ranges. The MSX transmitter can provide a linear pressure output or a linear velocity output with the square root extraction from the transmitter. Additional parameters have been included to expand the square root capability for calculating flow. Dual voltage and milliamp output signals can be used to provide both control and equipment output signal verification.

NIST CALIBRATION available in Product Configurator.

Please see Series AT-MSX for ATEX/IECEx approved.



⚠WARNING: This product can expose you to Styrene a chemical known to the State of California to cause Cancer and Bisphenol A (BPA) a chemical known to the State of California to cause reproductive toxicity. Click Here.

Product Applications

    • Filter monitoring in air handler units
    • Building pressure in pharmaceutical/semiconductor clean rooms
    • Duct static pressure in commercial buildings
    • Air velocity/flow in VAV systems
 
 
  • bvseo_sdk, java_sdk, bvseo-4.0.0
  • CLOUD, getReviews, 5ms
  • REVIEWS, PRODUCT
  • bvseo-msg: The resource to the URL or file is currently unavailable.;
  • bvseo_sdk, java_sdk, bvseo-4.0.0
  • CLOUD, getContent, 14ms
  • QUESTIONS, PRODUCT
  • bvseo-msg: The resource to the URL or file is currently unavailable.;
fr-CA
fr
Enregistrer la configuration