FE-HEATER
204 °C Max Constant Wattage Heating Cable 120-480 Vac
- Continuous Exposure Rating up to 400°F
- Low Watt Density
- Parallel Resistance Heater
- Cut-to- Length at the Job Site
FE-HEATER
Depuis
C$
11.58

L'aperçu du produit
- Approvals Group B
- Cable Length 1 ft
- Cable Length, Max 180 ft
- Cable Material Nickel, Copper
- Dielectric Strength 2500 V
- Heater Wire Material Nichrome
- Insulation 20 Mil FEP
- Module Length 2 ft
- Operating Temperature, Max 148 °C
- Operating Temperature Note Exposure Temperature: 0 to 204 °C; Short Term Exposure Temperature: 232 °C
- Purchase Note Use quantity to indicate length of cable to purchase (increments of 1 foot), min purchase of 25 ft
- Wire Gauge 12 AWG
- Wire Thickness 0.3 in
- Wire Width 0.2 in
The FE cable heating element is tension wrapped and covered with a fluorocarbon film and enclosed in a minimum 20 mil FEP abrasion resistant extruded jacket. This tough outer cover provides moisture and dielectric protection as well as resistance to abrasion.
A tinned copper overbraid provides additional protection and electrical ground return path.
APPLICATIONS
OMEGALUXâ„¢ FE cable is a low Watt density electrical resistance heater. It is designed for freeze protection and midrange process temperature control and maintenance applications in lines periodically purged with 150 PSIG steam.
# Cable circuit module length in feet. When ordering please allow a minimum of 1 module length extra for terminations.
**Maximum Circuit Lengths include end-to-end voltage variation of 10%. Longer runs may be used. Lengths are based on cable operating temperatures of 300°F.
To complete your system the following accessories are recommended: (1) Termination kits for FE cable (see page B-31 for specifications), (2) Control options - see Section P for complete selection of controllers thermostats.
A tinned copper overbraid provides additional protection and electrical ground return path.
APPLICATIONS
OMEGALUXâ„¢ FE cable is a low Watt density electrical resistance heater. It is designed for freeze protection and midrange process temperature control and maintenance applications in lines periodically purged with 150 PSIG steam.
Model No. | Watts/ft. | Volts | Module# Length (ft)1 | Max** Length (ft) |
FE3-120B | 3 | 120 | 2 | 360 |
FE3-240B | 3 | 240 | 4 | 720 |
FE5-120B | 5 | 120 | 2 | 275 |
FE5-240B | 5 | 240 | 3 | 550 |
FE8-120B | 8 | 120 | 2 | 220 |
FE8-208B | 8 | 208 | 4 | 381 |
FE8-240B | 8 | 240 | 4 | 440 |
FE8-277B | 8 | 277 | 4 | 508 |
FE8-480B | 8 | 480 | 6 | 880 |
FE12-120B | 12 | 120 | 2 | 180 |
FE12-208B | 12 | 208 | 4 | 312 |
FE12-240B | 12 | 240 | 2 | 360 |
FE12-277B | 12 | 277 | 4 | 416 |
**Maximum Circuit Lengths include end-to-end voltage variation of 10%. Longer runs may be used. Lengths are based on cable operating temperatures of 300°F.
To complete your system the following accessories are recommended: (1) Termination kits for FE cable (see page B-31 for specifications), (2) Control options - see Section P for complete selection of controllers thermostats.
PDF et manuels
Afficher les notes et les avis
We purchased 8’ of fe8-480b and only need 2’. Can it be cut? It didn’t come with ends. What should we order for that? It’s self regulating so do we need a temperature control?
The FE-UC-KIT is sold for terminating the cable which can be cut. It is self regulating so a Controller is not required though some type of over temperature device to detect and open the circuit if an excessive temperature is reached is advised.