UFM-DWG-Series
Clamp on Transit Time Ultrasonic Flow Meter For 2.5 in to 10 in Pipes
Modèles en stock
- Clamp-on, non-invasive Flow Meter
- Bidirectional flow measurement system
- Measures flow rate, total and velocity of water flow
- Set up the meter through keypad interface or with SoloCUE® Flow Device Manager software
UFM-DWG-Series
Depuis
C$
4 039.29
Modèles en stock

L'aperçu du produit
- Accuracy ± 1 %
- Calibration Option Factory Calibrated
- Certifications CE
- Data Interface BACnet MS/TP, Modbus RTU, USB
- Display Language English, French, German and Spanish selectable
- Display Note Keypad: 4-button navigation, membrane keypad with domed tactile feedback Resolution: 128 × 64 pixel LED backlit graphical display; adjustable brightness and timeout
- Display Type LED
- Electrical Output 4 to 20 mA, Two Pulse, Frequency
- Enclosure Ratings IP65
- Form factor Pipe Remote mount
- Keypad Yes
- Materials 316 Stainless Steel, Polycarbonate
- Measurement Type Transit Time
- Number of Outputs 4
- Operating Temperature, Max 60 °C
- Operating Temperature, Min -20 °C
- Output Detail Pulse / Frequency /Digital : Two outputs, each selectable as frequency, pulse, forward/reverse flow or alarm output; isolated open collector, 5-30V DC, 50 mA maximum, externally or internally sourced with pullup resistor Digital alarm output: configurable high or low Frequency output: 63 Hz-10 kHz maximum Pulse (totalizer) output: 100 Hz maximum output open collector, pulse width 5-500 ms programmable Analog Output: 0-20 mA and 4-20 mA drive up to 800 Ohms; minimum 16-bit resolution, isolated Open Collector Output: 5 to 30 Vdc, max. 50 mA externally or internally sourced
- Pipe Size, Max 10 in
- Pipe Size, Min 2.5 in
- Process Temperature, Min -40 °C
- Pulse Rates 100 Hz
- Repeatability ±0.2%
- Repeatability Note ±0.2% of reading
- Reserved Type Standard
- Software SoloCUE
- Storage Temperature, Max 80 °C
- Storage Temperature, Min -40 °C
- Supply Power Type DC
- Supply Voltage 9 to 28 Vdc
- Velocity, Max 40 ft/s
- Velocity, Min 0.1 ft/s
The TFX-500w transit time ultrasonic flow meter measures volumetric flow of clean water in pipes 10 in. or smaller. By clamping on the outside of the pipe, the ultrasonic meter installs without cutting or tapping the pipe.
APPLICATIONThe TFX-500w meter is well suited for building automation, water distribution and wastewater collection in new and retrofit applications. In addition to having lower installation costs than an inline flow meter, the TFX-500w meter can be installed while the system continues to operate without interruption.
The TFX-500w meter is suitable for:
• Potable water
• Reclaimed water
• Chiller water
• Boiler feed water
• Make-up water
• Condenser water
• Condensate
OPERATION
Transit time flow meters use two transducers that function as both ultrasonic transmitters and receivers. The flow meters operate by alternately transmitting and receiving a frequency-modulated burst of sound energy between the two transducers. The burst is first transmitted in the direction of fluid flow and then against fluid flow. Since sound energy in a moving liquid is carried faster when it travels in the direction of fluid flow (downstream) than it does when it travels against fluid flow (upstream), a differential in the times of flight will occur. The sound’s time-of-flight is accurately measured in both directions and the difference in time-of-flight calculated.
Transducers
Model | Construction | Cable Length | Pipe/Tubing Sizes |
---|---|---|---|
KZ (IP54), Standard pipe, Integrated rail | PBT glass filled, Ultem®, Nylon cord grip PVC cable jacket; –40…250° F (–40…121° C) | 100 ft (30 m) max | 2.5…10 in. (DN65…DN250) |
RZ (IP54), Standard pipe | PBT glass filled, Ultem®, Nylon cord grip PVC cable jacket; –40…250° F (–40…121° C) | 300 ft (90 m) max. | 2.5…10 in. (DN65…DN250) |
NZ (IP67), Standard pipe | CPVC, Ultem, Nylon cord grip Polyethylene cable jacket; –40…194° F (–40…90° C) | 300 ft (90 m) max | 2.5…10 in. (DN65…DN250) |
PDF et manuels
Logiciels et pilotes
Afficher les notes et les avis
Rated 5 out of
5
by
Vitalic from
Very slow customer service
Very slow customer support. Device has power and display backlight is on but no digits. Customer support tells me to check transformer fuses and power, doesn't understand device has power. Was able to connect with a USB cable and programmed it so there's a reading until I hear back from warranty department, which is not faster than customer service. It's been a few days and still waiting for anyone to follow up with me.
Date published: 2023-10-02
What is the maximum allowable piping insulation thickness (or does the instrument need to be in contact with outside wall of the piping)?
Thank you for your inquiry. The transducers must be in direct contact with the pipe wall inorder for the ultrasonic to penetrate thru and measure the flow rate.
Date published: 2025-01-30
What is the update rate of this flowmeter?
Thank you for your inquiry! The update rate can vary but the default damping setting for these units is 40 seconds. Please see page 28 of the manual for further information regarding settings that affect the response time of the unit.
Date published: 2022-05-23
Is there a limit/maximum of a steel pipe thickness for the flowmeter to work?
Thank you for your inquiry! The maximum wall thickness for the TFX-500W models is 1".
Date published: 2022-05-19
What is the minimum "straight run" of pipe that this can work with on 10" diameter pipe?
Thank you for your inquiry. The Rule of Thumb for straight run pipe is 10x the pipe diameter upstream and 5x downstream.
Date published: 2024-08-02