GCHI-GCHIB
Medium Temperature Steam, Air, Gas Circulation Heater
- 3 - 18' ANSI Blind Flange Design
- 3 - 18' Carbon Steel Pipe Body, 150 Lb Construction (750°F Max. Vessel and 1600°F Max. Sheath Temp.) 1 For Stainless Steel Pipe Body Construction, Refer to GCHIS Series Circulation Heaters.
- 3 - 350 kW
- 240 and 480V, 1 & 3 Phase

L'aperçu du produit
APPLICATIONS
Steam, Air and Gas: Higher kW ratings for larger industrial and commercial gas heating applications.
FEATURES Terminal Enclosure: E1 General Purpose is standard. E2 Moisture Resistant/Explosion Resistant, E3 Explosion Resistant or E4 Moisture Resistant available.
Elements: 0.475" diameter INCOLOY sheath elements.
Flange: 3 -10" ANSI B-16.5 flange with 1/2" thermowell for thermostat bulb and a 1/8" NPT threaded opening for a thermocouple or RTD.
Vessel: Pipe body and nozzles are ASTM A53B carbon steel pipe. The end disk is ASTM A516 Grade 70 carbon steel plate. Provided with thermal insulation and painted sheet metal jacket.
Baffle Assembly: Internal baffle assemblies are provided on GCHIB-18 models. Baffles reduce the internal cross sectional area thereby increasing the velocity of the gas. Increasing the gas velocity reduces the operating temperature of the elements and the shell of the vessel.
Wiring: Convenient field wiring terminals are provided for easy installation.
Controls: Series 03 and 06 stock and assembly stock heaters come equipped with side mounted thermostat. Series 18, 27, 45 and 108 are furnished without thermostat.

1. Outlet gas temperature must be kept below both maximum sheath and vessel temperature or element and heater damage may occur.
1. Outlet gas temperature must be kept below both maximum sheath and vessel temperature or element and heater damage may occur. Other Note — Refer to the Controls section for side mounted controls or control panels.
1. Recommended temperature limits for all GCH heaters with carbon steel vessels and INCOLOY elements are 1600oF maximum for the sheath temperature and 750°F maximum for the vessel temperature at 5 psi pressure maximum. Exceeding these recommendations will void the factory warranty. Outlet gas temperatures must be kept below both the maximum sheath and vessel temperature or element and vessel damage may occur. Heaters supplied without controls.
Other Note — Refer to the Controls section for side mounted controls or control panels.
Steam, Air and Gas: Higher kW ratings for larger industrial and commercial gas heating applications.
FEATURES Terminal Enclosure: E1 General Purpose is standard. E2 Moisture Resistant/Explosion Resistant, E3 Explosion Resistant or E4 Moisture Resistant available.
Elements: 0.475" diameter INCOLOY sheath elements.
Flange: 3 -10" ANSI B-16.5 flange with 1/2" thermowell for thermostat bulb and a 1/8" NPT threaded opening for a thermocouple or RTD.
Vessel: Pipe body and nozzles are ASTM A53B carbon steel pipe. The end disk is ASTM A516 Grade 70 carbon steel plate. Provided with thermal insulation and painted sheet metal jacket.
Baffle Assembly: Internal baffle assemblies are provided on GCHIB-18 models. Baffles reduce the internal cross sectional area thereby increasing the velocity of the gas. Increasing the gas velocity reduces the operating temperature of the elements and the shell of the vessel.
Wiring: Convenient field wiring terminals are provided for easy installation.
Controls: Series 03 and 06 stock and assembly stock heaters come equipped with side mounted thermostat. Series 18, 27, 45 and 108 are furnished without thermostat.

kW | Volts | Ckt & Phase | Dimensions (In.) | Model No . | Wt. (Lbs.) | ||
A | B | C | |||||
Series 03 — 3 inch, 150 lb carbon steel vessel — 3 INCOLOY elements1 (23 W/In2) with thermostat | |||||||
3 | 240 | 1-1 | 32 15/16 | 22 1/2 | 16 1/2 | GCHI-03-003P-E1/240 | 62 |
3 | 240 | 1-3 | 32 15/16 | 22 1/2 | 16 1/2 | GCHI-03-003P-E1/240/3P | 62 |
3 | 480 | 1-1 | 32 15/16 | 22 1/2 | 16 1/2 | GCHI-03-003P-E1/480 | 62 |
3 | 480 | 1-3 | 32 15/16 | 22 1/2 | 16 1/2 | GCHI-03-003P-E1/480/3P | 62 |
4.5 | 240 | 1-1 | 32 15/16 | 22 1/2 | 16 1/2 | GCHI-03-04P5-E1/240 | 72 |
4.5 | 240 | 1-3 | 32 15/16 | 22 1/2 | 16 1/2 | GCHI-03-04P5-E1/240/3P | 72 |
4.5 | 480 | 1-1 | 32 15/16 | 22 1/2 | 16 1/2 | GCHI-03-04P5-E1/480 | 72 |
4.5 | 480 | 1-3 | 32 15/16 | 22 1/2 | 16 1/2 | GCHI-03-04P5-E1/480/3P | 72 |
6 | 240 | 1-1 | 42 15/16 | 32 1/2 | 26 1/2 | GCHI-03-006P-E1/240 | 94 |
6 | 240 | 1-3 | 42 15/16 | 32 1/2 | 26 1/2 | GCHI-03-006P-E1/240/3P | 94 |
6 | 480 | 1-1 | 42 15/16 | 32 1/2 | 26 1/2 | GCHI-03-006P-E1/480 | 94 |
6 | 480 | 1-3 | 42 15/16 | 32 1/2 | 26 1/2 | GCHI-03-006P-E1/480/3P | 94 |
kW | Volts | Ckt & Phase | Dimensions (In.) | Model No . | Wt. (Lbs.) | ||
A | B | C | |||||
Series 06 — 5 inch, 150 lb carbon steel vessel — 6 INCOLOY elements1 (23 W/In2) with thermostat | |||||||
9 | 240 | 1-1 | 41 3/4 | 30 | 11 3/8 | GCHI-06-009P-E1/240 | 135 |
9 | 240 | 1-3 | 41 3/4 | 30 | 11 3/8 | GCHI-06-009P-E1/240/3P | 135 |
9 | 480 | 1-1 | 41 3/4 | 30 | 11 3/8 | GCHI-06-009P-E1/480 | 135 |
9 | 480 | 1-3 | 41 3/4 | 30 | 11 3/8 | GCHI-06-009P-E1/480/3P | 135 |
12 | 240 | 1-1 | 48 3/4 | 37 | 14 7/8 | GCHI-06-012P-E1/240 | 164 |
12 | 240 | 1-3 | 48 3/4 | 37 | 14 7/8 | GCHI-06-012P-E1/240/3P | 164 |
12 | 480 | 1-1 | 48 3/4 | 37 | 14 7/8 | GCHI-06-012P-E1/480 | 164 |
12 | 480 | 1-3 | 48 3/4 | 37 | 14 7/8 | GCHI-06-012P-E1/480/3P | 164 |
20 | 240 | 1-1 | 60 1/4 | 48 1/2 | 20 5/8 | GCHI-06-020P-E1/240 | 195 |
20 | 240 | 1-3 | 60 1/4 | 48 1/2 | 20 5/8 | GCHI-06-020P-E1/240/3P | 195 |
20 | 480 | 1-1 | 60 1/4 | 48 1/2 | 20 5/8 | GCHI-06-020P-E1/480 | 195 |
20 | 480 | 1-3 | 60 1/4 | 48 1/2 | 20 5/8 | GCHI-06-020P-E1/480/3P | 195 |
25 | 240 | 1-1 | 73 5/8 | 61 7/8 | 27 5/16 | GCHI-06-025P-E1/240 | 212 |
25 | 480 | 1-3 | 73 5/8 | 61 7/8 | 27 5/16 | GCHI-06-025P-E1/480/3P | 212 |
25 | 240 | 1-1 | 73 5/8 | 61 7/8 | 27 5/16 | GCHI-06-025P-E1/240 | 212 |
25 | 480 | 1-3 | 73 5/8 | 61 7/8 | 27 5/16 | GCHI-06-025P-E1/480/3P | 212 |
30 | 240 | 1-3 | 86 5/8 | 74 7/8 | 33 7/8 | GCHI-06-030P-E1/240/3P | 240 |
30 | 480 | 1-3 | 86 5/8 | 74 7/8 | 33 7/8 | GCHI-06-030P-E1/480/3P | 240 |
Series 18 — 8 inch, 150 lb carbon steel vessel — 18 baffled INCOLOY elements1 (20 W/In2) | |||||||
30 | 240 | 3-3 | 54 5/16 | 32 11/16 | 29 3/16 | GCHIB-18-030P-E1/240 | 350 |
30 | 480 | 3-3 | 54 5/16 | 32 11/16 | 29 3/16 | GCHIB-18-030P-E1/480 | 350 |
40 | 240 | 3-3 | 61 5/16 | 39 11/16 | 36 3/16 | GCHIB-18-040P-E1/240 | 420 |
40 | 480 | 3-3 | 61 5/16 | 39 11/16 | 36 3/16 | GCHIB-18-040P-E1/480 | 420 |
50 | 240 | 3-3 | 68 15/16 | 47 5/16 | 43 3/16 | GCHIB-18-050P-E1/240 | 480 |
50 | 480 | 3-3 | 68 15/16 | 47 5/16 | 43 3/16 | GCHIB-18-050P-E1/480 | 480 |
Series 27 — 10 inch, 150 lb carbon steel vessel — 27 INCOLOY® elements1 (15 W/In2) | |||||||
50 | 240 | 3-3 | 68 9/16 | 43 | 39 1/2 | GCHI-27-050P-E1/240 | 400 |
50 | 480 | 3-3 | 68 9/16 | 43 | 39 1/2 | GCHI-27-050P-E1/480 | 400 |
60 | 240 | 3-3 | 75 9/16 | 50 | 46 1/2 | GCHI-27-060P-E1/240 | 440 |
60 | 480 | 3-3 | 75 9/16 | 50 | 46 1/2 | GCHI-27-060P-E1/480 | 440 |
70 | 240 | 3-3 | 81 9/16 | 56 | 52 1/2 | GCHI-27-070P-E1/240 | 480 |
70 | 480 | 3-3 | 81 9/16 | 56 | 52 1/2 | GCHI-27-070P-E1/480 | 480 |
80 | 240 | 3-3 | 91 9/16 | 66 | 62 1/2 | GCHI-27-080P-E1/240 | 520 |
80 | 480 | 3-3 | 91 9/16 | 66 | 62 1/2 | GCHI-27-080P-E1/480 | 520 |
90 | 240 | 3-3 | 100 9/16 | 75 | 71 1/2 | GCHI-27-090P-E1/240 | 560 |
90 | 480 | 3-3 | 100 9/16 | 75 | 71 1/2 | GCHI-27-090P-E1/480 | 560 |
kW | Volts | Ckt & Phase | Dimensions (In.) | Model No . | Wt. (Lbs.) | ||||
A | B | C | D | E | |||||
Series 45 — 14 inch, 150 lb carbon steel vessel — 45 INCOLOY elements1 (15 W/In2) | |||||||||
75 | 480 | 3-3 | 76 | 57 3/16 | 66 11/16 | 15 | 11 1/2 | GCHI-45-075P-E1/480 | 835 |
90 | 480 | 3-3 | 76 | 57 3/16 | 66 11/16 | 15 | 11 1/2 | GCHI-45-090P-E1/480 | 925 |
125 | 480 | 3-3 | 91 | 72 3/16 | 81 11/16 | 15 | 11 1/2 | GCHI-45-125P-E1/480 | 1025 |
150 | 480 | 3-3 | 106 | 87 3/16 | 96 11/16 | 15 | 11 1/2 | GCHI-45-150P-E1/480 | 1125 |
175 | 480 | 3-3 | 121 | 102 3/16 | 111 11/16 | 15 | 11 1/2 | GCHI-45-175P-E1/480 | 1225 |
Series 72 — 16 inch, 150 lb carbon steel vessel — 72 INCOLOY elements1 (15 W/In2) | |||||||||
200 | 480 | 3-3 | 93 | 74 5/8 | 84 1/8 | 16 | 12 3/4 | GCHI-72-200P-E1/480 | 1265 |
225 | 480 | 3-3 | 101 | 82 5/8 | 92 1/8 | 16 | 12 3/4 | GCHI-72-225P-E1/480 | 1310 |
250 | 480 | 3-3 | 109 | 90 5/8 | 100 1/8 | 16 | 12 3/4 | GCHI-72-250P-E1/480 | 1355 |
Series 108 — 18 inch, 150 lb carbon steel vessel — 108 INCOLOY elements1 (15 W/In2) | |||||||||
300 | 480 | 6-3 | 94 | 75 1/2 | 85 | 17 | 13 1/2 | GCHI-108-300P-E1/480 | 1400 |
325 | 480 | 6-3 | 100 | 81 1/2 | 91 | 17 | 13 1/2 | GCHI-108-325P-E1/480 | 1450 |
350 | 480 | 6-3 | 106 | 87 1/2 | 97 | 17 | 13 1/2 | GCHI-108-350P-E1/480 | 1500 |
Other Note — Refer to the Controls section for side mounted controls or control panels.