1-800-663-4209 | Vos commentaires sont importants, répondez à un sondage rapide commentaires sur le site web

PCM5-Series
PCM5 convert a 4 to 20 mA signal to a time proportional output
Modèles en stock
- Tolerates Inputs Less than 4 mA
- Converts 4 to 20 mA to a Time Proportional Output
- Mounts Directly on a Single 3 to 32 VdcInput SSR
- Supports Single Phase 50 or 60 Hz Operation

L'aperçu du produit
- Frequency 50 to 60 Hz
- Input Control Signal 3 to 32 Vdc
- Operating Temperature, Max 40 °C
- Operating Temperature, Min 0 °C
The OMEGA PCM5 Series converter is designed to convert a 4 to 20 mA signal from a process/ temperature controller or computer to a time proportional output.
The modules mount directly to the input terminals on a 3 to 32 Vdc input SSR, and supports single phase 50 or 60 Hz operation. Lever clamps are provided on the converter for the 4 to 20 mA input. The SSR’s power section provides easy connection to the line and load.
SPECIFICATIONS
Analog Input Signal:4 to 20 mA minimal; 0 to 30 mA permissible; reverse polarity protected; no abnormal operation below 4 mA
Compliance Voltage Requirement:6.4V
Time Base:~200 mS @ 50%, ~500 mS towards 0 and 100%
Ambient Temperature:0 to 40°C (32 to 104°F)
Dimensions:45 L x 51 W x 20 mm D (1.75 x 2.0 x 0.80")
The modules mount directly to the input terminals on a 3 to 32 Vdc input SSR, and supports single phase 50 or 60 Hz operation. Lever clamps are provided on the converter for the 4 to 20 mA input. The SSR’s power section provides easy connection to the line and load.
SPECIFICATIONS
Analog Input Signal:4 to 20 mA minimal; 0 to 30 mA permissible; reverse polarity protected; no abnormal operation below 4 mA
Compliance Voltage Requirement:6.4V
Time Base:~200 mS @ 50%, ~500 mS towards 0 and 100%
Ambient Temperature:0 to 40°C (32 to 104°F)
Dimensions:45 L x 51 W x 20 mm D (1.75 x 2.0 x 0.80")
PDF et manuels
Afficher les notes et les avis
Does the PCM5 require voltage to power it up? If so how many amps? Where do you plug the input power in? What do the 2 pots do please? Can you adjust the time duration of the pulse to 1 second?
Thank you for your inquiry. 3 to 32 VDC at 4-20mA to power it. Please see manual for wiring diagram.
Date published: 2020-07-14
Are the pots for zero and span adjustments. Adjust the Zero so no output until input get to 40 % ie 10.4 ma' Span would be set at 20ma output so 40 to 100% input = 0 to 100% output
Hi Randy
Pots are set at factory so that a 4 mA you have no pulse output. At 20 mA you would have constant on cycle. At 12 mA you have 50% on time with a time base of 200 mS.
Best regards,
OMEGA
Date published: 2024-04-01