PX3005-DIFF
Rangeable, Differential Pressure Transmitters with Display
Modèles en stock
- 0.075% Accuracy
- Linear or Square Root Output
- Adjustable Pulsation Dampening
- LCD Displays Either Process Variable, mA, or %
PX3005-DIFF
Depuis
C$
1,416.78
Modèles en stock

L'aperçu du produit
- Accuracy ± 0.075 %
- Accuracy Class < 0.1%
- Accuracy Note Accuracy (NLHR, 20°C ± 5°C): ± 0.075TD% SPAN (Square root output accuracy is 1.5 times linear output accuracy)
- Additional Features 1 Rangable with 5 digit display
- Damping Time 0 to 100 sec
- Electrical Connection M12 4 pin
- Electrical Output 4 to 20 mA
- Electrical Output Note 4 to 20mA Two wire, linear or square root output selectable
- Enclosure Material 316L Stainless Steel
- Enclosure Ratings IP67
- Fill Fluid Silicon oil
- Loop Resistance, Max <(U-10.5)/0.021Ω, where U is supply voltage
- Materials, Wetted 316 Stainless Steel, FKM
- Media Compatibility Air, Alkaline solutions, Any, Argon, Carbon dioxide, Dilute Acids, Gases, Helium, Hydraulic Oil, Hydrogen, Light Oil, Liquids, Nitrogen, Non-corrosive Dry Gasses, Oil, Oxygen, Solvents, Steam, Water, Water-based fluids
- Operating Temperature, Max 70 °C
- Operating Temperature, Min -20 °C
- Output Signal Current
- Position Effect Install error less than 400Pa (1.60” H2O) can be corrected by PV = 0 reset
- Power Supply 500 mW
- Pressure Type Differential
- Process Connection Size 1/4 in
- Process Connection Type NPT Female
- Process Temperature, Max 120 °C
- Process Temperature, Min -40 °C
- Response Time 200 ms
- Stability ± 0.2%
- Stability Note ± 0.2% 60 months
- Storage Temperature, Max 85 °C
- Storage Temperature, Min -40 °C
- Supply Voltage 10.5 to 55 Vdc
- Thermal Effect on Zero error, Max ± (0.1 +0.1TD)% SPAN
- Transmission Distance up to 1000 meters
- Vibration Effect GB/T 1827.3/IEC61298-3 tests, 20g (5 to 2000 HZ, max <± 3 mm), <0.1% URL
- Weight 3 kg
The Omega differential PX3005-DIFF is a compact, rangeable, pressure transmitter ideal for monitoring pressures in process automation, hydraulic systems, compressors, pumps, and in tank level applications where consistent, reliable pressure measurement is essential. The PX3005-DIFF utilizes a unique encapsulation construction of a MEMs piezoresistive pressure sensor coupled to an advanced microprocessing to provide superior accuracy and performance.
The unique construction enables high line pressure operations and superior protection from pressure overloads. The rugged 316 stainless-steel enclosure is IP67 rated making it suitable for wash down environments. A 5-digit backlit LCD allows for a full precision representation of process variable. Available in ranges from 1 to 1,500 psi, the intelligent transmitter module allows for configuration of the 4 to 20 mA signal, display of input or output, and choice of 19 measurement units. The output signal can be adjusted to re-arrange the transmitter or “tare” unwanted fluid head preloads. Rangeability is capable of adjusting zero and span are from -100 to 100% FS URL (Upper Range Limit) with a minimum span of 30% URL. This means a 15 psi transducer can have the zero set between -15 to FS 15 psi. For example, zero could be set for -15 psi and maximum 15 psi so the output would be 4 mA at -15 psi, midpoint 12 mA would be 0 psi and 20 mA would be 15 psi.
Dimensions: mm (inches)

Specifications
Turndown = nominal range of the device / set span of device
EXAMPLE: a PX3005-1KWDWBI with set span of 500"H2O TD = 1000"H2O/500"H2O = 2
Accuracy (NLHR, 20°C ± 5°C): ± 0.075TD% SPAN
(Square root output accuracy is 1.5 times linear output accuracy)
Long Term Stability: ± 0.2% URL/60 months
Ambient Temperature Effects -20 to 80°C (-4 to 176°F): ± (0.1 +0.1TD)% SPAN
Static Pressure Effects: Effect on zero ± 0.15TD % SPAN/10MPa (1450 psi); Effect on full scale ± 0.2% SPAN/10 MPa (1450 psi)
Power Supply Effects: ± 0.005TD% SPAN/V (Zero and Span)
Mounting Position Effects: Install error less than 400Pa (1.60” H2O) can be corrected by PV = 0 reset
Vibration Effects: GB/T 1827.3/IEC61298-3 tests, 20g (5 to 2000 HZ, max <± 3 mm), <0.1% URL
Supply Voltage (U): 10.5 to 55VDC
Output Signal: 4 to 20mA Two wire, linear or square root output selectable
Sensor Response Time: 200 mS
Damping Time: Selectable, 0 to 100 S
Load Resistance Ω: <(U-10.5)/0.021
Transmission Distance: < 1000 m
Power Consumption: 500mW (20.8mA output @ 24VDC)
Operating Temperature: -20 to 70°C (-4 to 160°F)
Storage Temperature: -40 to 85°C (-40 to 185°F)
Media Temperature: -40 to 120°C (-40 to 250°F)
Environmental Rating: IP67
Media: Fluids and gasses compatible with 316 SS
Process Connection/Material: ¼" -18NPT F/316 SS
Electrical Connection: 4 pin male M12
Isolating Diaphragm: 316L SS
Sensor Fill Fluid: Silicone Oil
Sensor Seal: O-ring, FKM
Housing Material: 316 SS
Weight:
Net Weight: about 3kg (without mounting bracket and process connection adaptor)
Range Limit Table
EMC Environment:
GB/T 9254/CISPR22
GB/T 17626.2/IEC61000-4-2
GB/T 17626.3/IEC61000-4-3
GB/T 17626.8/IEC61000-4-8
GB/T 17626.4/IEC61000-4-4
GB/T 17626.5/IEC61000-4-5
GB/T 17626.6/IEC61000-4-6
The unique construction enables high line pressure operations and superior protection from pressure overloads. The rugged 316 stainless-steel enclosure is IP67 rated making it suitable for wash down environments. A 5-digit backlit LCD allows for a full precision representation of process variable. Available in ranges from 1 to 1,500 psi, the intelligent transmitter module allows for configuration of the 4 to 20 mA signal, display of input or output, and choice of 19 measurement units. The output signal can be adjusted to re-arrange the transmitter or “tare” unwanted fluid head preloads. Rangeability is capable of adjusting zero and span are from -100 to 100% FS URL (Upper Range Limit) with a minimum span of 30% URL. This means a 15 psi transducer can have the zero set between -15 to FS 15 psi. For example, zero could be set for -15 psi and maximum 15 psi so the output would be 4 mA at -15 psi, midpoint 12 mA would be 0 psi and 20 mA would be 15 psi.
Dimensions: mm (inches)

Specifications
Turndown = nominal range of the device / set span of device
EXAMPLE: a PX3005-1KWDWBI with set span of 500"H2O TD = 1000"H2O/500"H2O = 2
Accuracy (NLHR, 20°C ± 5°C): ± 0.075TD% SPAN
(Square root output accuracy is 1.5 times linear output accuracy)
Long Term Stability: ± 0.2% URL/60 months
Ambient Temperature Effects -20 to 80°C (-4 to 176°F): ± (0.1 +0.1TD)% SPAN
Static Pressure Effects: Effect on zero ± 0.15TD % SPAN/10MPa (1450 psi); Effect on full scale ± 0.2% SPAN/10 MPa (1450 psi)
Power Supply Effects: ± 0.005TD% SPAN/V (Zero and Span)
Mounting Position Effects: Install error less than 400Pa (1.60” H2O) can be corrected by PV = 0 reset
Vibration Effects: GB/T 1827.3/IEC61298-3 tests, 20g (5 to 2000 HZ, max <± 3 mm), <0.1% URL
Supply Voltage (U): 10.5 to 55VDC
Output Signal: 4 to 20mA Two wire, linear or square root output selectable
Sensor Response Time: 200 mS
Damping Time: Selectable, 0 to 100 S
Load Resistance Ω: <(U-10.5)/0.021
Transmission Distance: < 1000 m
Power Consumption: 500mW (20.8mA output @ 24VDC)
Operating Temperature: -20 to 70°C (-4 to 160°F)
Storage Temperature: -40 to 85°C (-40 to 185°F)
Media Temperature: -40 to 120°C (-40 to 250°F)
Environmental Rating: IP67
Media: Fluids and gasses compatible with 316 SS
Process Connection/Material: ¼" -18NPT F/316 SS
Electrical Connection: 4 pin male M12
Isolating Diaphragm: 316L SS
Sensor Fill Fluid: Silicone Oil
Sensor Seal: O-ring, FKM
Housing Material: 316 SS
Weight:
Net Weight: about 3kg (without mounting bracket and process connection adaptor)
Range Limit Table
Nominal Value | Minimum Span | UPPER (URL) | LOWER (LRL) | Static pressure limit | Hi Side Over Range Limit | Lo Side Over Range Limit | |||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|
mbar | "H2O | mbar | "H2O | mbar | "H2O | mbar | "H2O | bar | psi | bar | psi | bar | psi |
60 | 25 | 0.02 | 0.8 | 60 | 25 | -60 | -25 | 250 | 3600 | 250 | 3600 | 160 | 2300 |
400 | 160 | 0.04 | 1.6 | 400 | 160 | -400 | -160 | 400 | 5750 | 250 | 3600 | 160 | 2300 |
2500 | 1000 | 0.25 | 10 | 2500 | 1000 | -2500 | -1000 | 400 | 5750 | 250 | 3600 | 160 | 2300 |
bar | psi | bar | psi | bar | psi | bar | psi | bar | psi | bar | psi | bar | psi |
10 | 150 | 0.1 | 1.5 | 10 | 150 | -5 | -70 | 400 | 5750 | 250 | 3600 | 160 | 2300 |
30 | 400 | 0.3 | 4 | 30 | 400 | -5 | -70 | 400 | 5750 | 250 | 3600 | 160 | 2300 |
100 | 1500 | 1 | 15 | 100 | 1500 | -5 | -70 | 400 | 5750 | 250 | 3600 | 160 | 2300 |
EMC Environment:
GB/T 9254/CISPR22
GB/T 17626.2/IEC61000-4-2
GB/T 17626.3/IEC61000-4-3
GB/T 17626.8/IEC61000-4-8
GB/T 17626.4/IEC61000-4-4
GB/T 17626.5/IEC61000-4-5
GB/T 17626.6/IEC61000-4-6
PDF et manuels
Afficher les notes et les avis
Rated 5 out of
5
by
Allen O from
Excellent product!
Easy setup, easy calibration, excellent build quality. An outstanding, cost effective transmitter.
Date published: 2020-04-23
In the data specs, is "TD" referring to "Total Differential"?
TD means Turn Down, it is the ratio of the full-scale output over the current scaled output.
Turndown = nominal range of the device/set span of the device
Date published: 2023-12-18
Being outside the measurement range, can I have one side at 1 bar and the other at 100 bar? Or do I break the membrane ? (e.g. PX3005-150dwi sensors)
Hello, we do not recommend using this device outside the calibrated range. The diaphragm could see plastic deformation that could affect your zero and span balance. It would be best to go with a higher range.
Date published: 2024-07-08
Good afternoon, I need a pressure differential transmitter that measures 50 psi on one side and 14.13 psi on the other.
Tank you for your inquire.
There a multiple choices and delivery times may be a factor. Please contact us directly.
Date published: 2022-06-06
What is the approximate volume of one side of the cell? (We need to fill one side of a cell that is already installed with a relatively exotic fluid)
Cavity volume of the process connection on the PX3005 Differential Transmitters in not readily available. Please contact our pressure product applications engineers directly at pressure@omgea.com. They will assist you in acquiring this information.
Date published: 2023-09-25
wich cable shoud I use for computer connection? is it this one "Twist Lock Connectors for Pressure Transducers and Load Cells''
Bramay, no cable we have will help you connect to a computer. You will need a data acquisition system. Please email us at das@dwyeromega.com for help selecting a DAS device.
Date published: 2024-06-19
Of the ports that are marked (H) and (L), which of the two is the (IN) port and which one is the (OUT) port.?
This is not a flow through sensor. The pressure applied to each port react on a internal diaphragm. The unit internally calculates the differential between the two applied pressures and output a signal represents this differential.
Date published: 2022-10-13
Just to confirm. The "WET/WET" means it is measuring pressure differential in fluid not in gasses. Correct?
Thank you for your inquire
The units that state wet wet can be used in liquid or gas.
Date published: 2020-12-18
I can range the -1000 to 1000 "H2O DP Transmitter to 0-278 "H2O. correct?
Yes they can. These unit are actually scalable so you can turn down the range of the unit do give you the full 4 to 20mA output signal over 0 to 278" wc.
Date published: 2021-02-09