Skip to search Skip to main content Skip to navigation

Welcome to our new website, found an issue or bug? Please report it here

We noticed you are from . Visit your local site for regional offers and live support.

DRC-4710-4720-Sig-Cond

DIN Rail Bridge Input Conditioners for Load Cell or Strain Gage

  • DIN Rail Mount
  • Bridge Input (Load Cell, Strain Gage) or Voltage Input
  • 0 to 10 Vdc (DRC-4710) or 4 to 20 mA (DRC-4720) Output
  • Economical
DRC-4710-4720-Sig-Cond
From C$ 427.84
DIN Rail Bridge Input Conditioners for Load Cell or Strain Gage DRC-4710-4720-Sig-Cond DRC-4710-4720-Sig-Cond
loading all models
Product Overview
  • Bandwidth DC to 10 Hz
  • CMRR 100 dB (dc)
  • Common Mode Voltage 0 to 5V
  • Height 96 mm
  • Input Noise Voltage 0.3 µV pp typ (0.1 to 10 Hz);
  • Input Range Note Input Range: 0 to 10 mV, 0 to 20 mV, 0 to 30 mV (dip switch selectable), Input Current (One 350 Ω Bridge): 40 mA
  • Input Type Voltage
  • Length 42 mm
  • Linearity ±0.01%
  • Mounting DIN Rail Mount
  • Number of Inputs 1
  • Offset Input Offset Voltage: ± 70 µV
  • Operating Temperature, Max 55 °C
  • Operating Temperature, Min 0 °C
  • Output Detail Fixed Output: 10V ±1.0%
  • Output Value Process
  • Storage Temperature, Max 80 °C
  • Storage Temperature, Min -40 °C
  • Supply Power Type DC
  • Supply Voltage 18 to 26 Vdc
  • Temperature Coefficient 0.05%/°C
  • Temperature Coefficient Note Input : 0.05%/°C Input Offset Voltage Temperature Coefficient : 0.7 µV/°C BRIDGE: 0.05%/°C Output ( Total RMS gain temperature Coefficient : 0.007%/°C
  • Voltage Measurement Range 0 to 30 mV dc
  • Voltage Output Range 0 to 10 Vdc
  • Weight 85 g
  • Width 27 mm
  • Zero Setting Adjustable Range 20% max output

Description

The DRC-4710 and DRC-4720 DIN rail mount signal conditioners are self-contained DC powered modules designed for bridge input (load cell, strain gage) or voltage input (not connected to a bridge, excitation supply not used). These signal conditioners contain a precision instrumentation amplifier, filtered output and a built-in 10V excitation supply capable of driving a 350 Ω bridge.

The 0 to 30 mV input range makes the DRC-4710 and DRC-4720 compatible with most strain gage based load cell or pressure transducer outputs. Two models are available, one with 0 to 10 Vdc output (DRC-4710), and the other with 4 to 20 mA output (DRC-4720). Connections are made via easily accessible screw terminal blocks. Zero and Span adjustment potentiometers are located externally as well for easy access.

Specifications
INPUT
Input Range:
0 to 10 mV, 0 to 20 mV, 0 to 30 mV (dip switch selectable)
Power: 18 to 26 Vdc (350 „¦ Bridge)
Linearity:
± 0.01%
Temperature Coefficient: 0.05%/°C
Input Offset Voltage: ± 70 µV
Input Offset Voltage Temperature Coefficient: 0.7 µV/°C
Common Mode Voltage: 0 to 5V
Common Mode Rejection (DC): 100 dB
Input Noise: 0.3 µV pp typ (0.1 to 10 Hz)

OUTPUT
Output Range: DRC-4710:
0 to 10 Vdc
DRC-4720: 4 to 20 mA
Load Current (DRC-4710): 5 mA max
Compliance Voltage (DRC-4720): 5.5V max
Loop Resistance (DRC-4720): 250 Ω max
Frequency Response (2-Pole Filter): DC to 10 Hz
Total RMS Gain Temperature Coefficient: 0.007%/°C

BRIDGE EXCITATION SUPPLY
Fixed Output:
10V ± 1.5%
Temperature Coefficient: 0.05%/°C
Load Current: 30 mA max

GENERAL Power: 18 to 26 Vdc
Power Consumption (One 350 Ω Bridge):
DRC-4710: 0.96 W (40 mA @ 24 Vdc)
DRC-4720: 1.32 W (55 mA @ 24 Vdc)
Operating Ambient: 0 to 55°C (32 to 131°F)
Storage Temperature: -40 to 80°C (-40 to 176°F)
Dimensions: 96 H x 27 W x 42 mm D (3.78 x 1.06 x 1.65")
Weight: 85 g (3 oz)
Rated 5 out of 5 by from Good conditioners - work well We have several instruments that came with Weidmuller conditioners, but they were not stable... drifted up and down over time. I replaced them with these Omega conditioners and we've had no further issues. Rock solid and work well. My only copmplaint would be that the terminal blocks are on the tiny side, and different front to back. I had to dig around to find a screwdriver small enough to fit the block.
Date published: 2016-10-20
Rated 4 out of 5 by from GOOD PRODUCT This product has been a outstanding part for us. Been using for 10 years.
Date published: 2022-03-22
Rated 1 out of 5 by from Wrong Item - Hard to Return This load cell amplifier was recommended for the 120 Ohm load cells. However, it can only drive 300 Ohm load cells. I'm working on returning it, but Omega is dragging their feet.
Date published: 2020-10-26
Rated 5 out of 5 by from Simple, easy to use Simple product, straightforward and easy to use. I was able to implement this product very quickly right out of the box. We consistently use them for taking load cell measurements and have never had any problems.
Date published: 2016-10-17
  • y_2025, m_2, d_20, h_8
  • bvseo_bulk, prod_bvrr, vn_bulk_3.0.42
  • cp_1, bvpage1
  • co_hasreviews, tv_0, tr_4
  • loc_en_CA, sid_DRC-4710, prod, sort_[SortEntry(order=HELPFULNESS, direction=DESCENDING), SortEntry(order=POSITIVE_FEEDBACK, direction=DESCENDING), SortEntry(order=SUBMISSION_TIME, direction=DESCENDING)]