Skip to search Skip to main content Skip to navigation

Welcome to our new website, found an issue or bug? Please report it here

We noticed you are from . Visit your local site for regional offers and live support.

DRSL-LPI-Srs-Loop-Pwr-Iso

DIN Rail Input Loop Powered Isolators w/ 1 or 2 Channel Models

Models In Stock
  • 1 Channel (DRSL-LPI-1) or 2 Channel (DRSL-LPI-2) Input Loop Powered Isolators
  • Powered by the Analog Input Current Signal Loop
  • 1:1 Signal Ratio
  • Low Input Voltage Drop
DRSL-LPI-Srs-Loop-Pwr-Iso
From C$ 212.16
Models In Stock
DIN Rail Input Loop Powered Isolators w/ 1 or 2 Channel Models DRSL-LPI-Srs-Loop-Pwr-Iso DRSL-LPI-Srs-Loop-Pwr-Iso
loading all models
Product Overview
  • Accuracy ±10 µA + 0.05 %
  • Approvals CE, UL, RoHS
  • Bandwidth 100 Hz
  • Calibration Temperature, Max 28 °C
  • Calibration Temperature, Min 20 °C
  • Conversion Rate 1:1
  • Current Measurement Range 0 to 20.5 mA
  • Electrical Output 0 to 20 mA
  • EMC Immunity Note Extended EMC Immunity NAMUR NE 21, A Criterion, Burst: <±1% of span
  • EMC Standard NAMUR NE 21
  • Enclosure Ratings IP20
  • Height 113 mm
  • Input Range Note Current; Signal Conversion: 1 to 1; Functional Range: 0 to 23 mA (NAMUR NE43 compliant); Start up Current: 10 µA typical; Input Overload: 50 mA max; Input to Output Voltage Drop:1.25V + (0.015 x Vout)where Vout = Iout x Routput, typical; Input Voltage Drop:(Unit voltage drop) + Vout
  • Input Type Current
  • Installation Pollution degree 2 and measurement/overvoltage category II
  • Isolation Isolation Voltage (Test): 2.5 kVac ;Isolation Voltage (Working):300 Vac
  • Length 115 mm
  • Mounting DIN Rail 35 mm Standard, EN 60715
  • Noise Calibration >60 dB
  • Operating Temperature, Max 70 °C
  • Operating Temperature, Min -25 °C
  • Output Detail Output Load: 600Ω max Output Load Stability: <0.01% of span/100 Ω (span = 0 to 20 mA) Voltage Limit: 17.5V
  • Output Signal Current
  • Output Value Process
  • Power Consumption 30 mW
  • Relative Humidity 0 to 95% RH (non-condensing)
  • Response Time < 5 ms
  • Response Time Note Response Time (0 to 90%, 100 to 10%): <5 ms
  • Screw Terminal Torque 0.5 Nm
  • Stability Load Stability: ≤0.01% of span/100 Ω
  • Storage Temperature, Max 85 °C
  • Storage Temperature, Min -40 °C
  • Supply Power Type Loop Powered
  • Temperature Coefficient ≤±2 µA/°C
  • Voltage Loss (Unit voltage drop) + Vout
  • Weight 70 g
  • Width 6.1 mm
  • Wire Gauge 26 to 12 AWG
The DRSL-LPI Series DIN rail input loop powered isolators provide a competitive choice in terms of both price and technology for galvanic isolation of current signals to SCADA systems or PLC equipment. These units provide isolation and 1:1 conversion of standard current signals and are powered by the analog input current signal loop.

The DRSL-LPI series offers isolation between input and output, provides surge suppression and protects control systems from transients and noise. These units also eliminate ground loops and can be used for measuring floating signals. Low power consumption facilitates DIN rail mounting without the need for any air gap. Measurement ranges are factory calibrated. These isolators operates over a wide temperature range from -25 to 70°C (-13 to 158°F).

SPECIFICATIONS
NUMBER OF CHANNELS
DRSL-LPI-1: 1
DRSL-LPI-2: 2
CURRENT INPUT
Signal Range (Input to Output): 0 to 20.5 mA
Signal Conversion: 1 to 1
Functional Range: 0 to 23 mA (NAMUR NE43 compliant)
Start up Current: 10 µA typical
Input Overload: 50 mA max
Input to Output Voltage Drop: 1.25V + (0.015 x Vout) where Vout = Iout x Routput, typical
Input Voltage Drop: (Unit voltage drop) + Vout
CURRENT OUTPUT
Output Load: 600Ω max
Output Load Stability: <0.01% of span/100 Ω (span = 0 to 20 mA)
Voltage Limit: 17.5V

GENERAL
Internal Consumption: 30 mW per channel
Isolation Voltage (Test): 2.5 kVac
Isolation Voltage (Working): 300 Vac
Signal/Noise Ratio: >60 dB
Cut-Off Frequency (3 dB): 100 Hz
Response Time (0 to 90%, 100 to 10%): <5 ms
Absolute Accuracy (at 25°C): ≠¤± 10 µA + 0.05% of max value of selected span
Temperature Coefficient: ≠¤± 2 µA/°C
EMC Immunity Influence: <± 0.5% of span
Extended EMC Immunity NAMUR NE 21, A Criterion, Burst: <± 1% of span

ENVIRONMENTAL
Operating Temperature: -25 to 70°C (-13 to 158°F)
Storage Temperature: -40 to 85°C (-40 to 185°F)
Calibration Temperature: 20 to 28°C (68 to 82°F)
Relative Humidity: 0 to 95% RH non-condensing
Protection Degree: IP20
Installation Area: Pollution degree 2 and measurement/overvoltage category II

MECHANICAL
Dimensions: 113 H x 6.1 W x 115 mm D (4.4 x 0.24 x 4.5")
Weight: 70 g (0.15 lb) approx
DIN Rail Type: DIN EN 60715 - 35 mm
Wire Size: 0.13 x 2.5 mm²/AWG 26 to 12 stranded wire
Screw Terminal Torque: 0.5 Nm
  • bvseo_sdk, java_sdk, bvseo-4.0.0
  • CLOUD, getReviews, 3ms
  • REVIEWS, PRODUCT
  • bvseo-msg: The resource to the URL or file is currently unavailable.;
  • bvseo_sdk, java_sdk, bvseo-4.0.0
  • CLOUD, getContent, 3ms
  • QUESTIONS, PRODUCT
  • bvseo-msg: The resource to the URL or file is currently unavailable.;
en-CA
en_CA
Save Configuration