Welcome to our new website, found an issue or bug? Please report it here
DRSL-RTD
RTD Input DIN Rail Signal Conditioners

Volume discounts available
Volume Discount Schedule
Quantity | Price each |
---|---|
1-4 | C$201.77 |
5-9 | C$191.68 |
10-24 | C$187.65 |
25-49 | C$179.58 |
50-99 | C$175.54 |
100+ | C$171.50 |
Added to Your Shopping Cart
Configuration complete.
Please add to cart to keep it or exit the configuration
Please add to cart to keep it or exit the configuration
Failed to Save Configurations, Click on Configure Button Start Again
Product Specs
<< See all Product ModelsBrand |
![]() |
Accuracy | ± 0.1 % |
Accuracy Note | Better than 0.2°C or ±0.1% of selected range |
Approvals | CE, UL, RoHS |
Calibration Temperature, Max | 28 °C |
Calibration Temperature, Min | 20 °C |
EMC Immunity Note | NAMUR NE 21, A Criterion, Burst: <±1% of span (span = selected input range) |
EMC Standard | NAMUR NE 21 |
Electrical Output | 4 to 20 mA |
Enclosure Ratings | IP20 |
Height | 113 mm |
Input Range Note | Sensor Current, RTD: <150 µA;Sensor Cable Specifications: 50 Ωper wire or 50 nF;Effect of Sensor Cable Resistance (3 or 4-wire RTD): <0.002 Ω/Ω;Broken Sensor Detection: >800 Ω;Shorted Sensor Detection: <18 Ω |
Input Type | RTD |
Installation | Pollution degree 2 and measurement/overvoltage category II |
Length | 115 mm |
Load Resistance | Current Output : 21 mA/600Ω /12.6V max;Voltage Output:>10 kΩ min |
Mounting | DIN Rail 35 mm Standard, EN 60715 |
Noise Calibration | >60 dB |
Number of Inputs | 1 |
Operating Temperature, Max | 70 °C |
Operating Temperature, Min | -25 °C |
Output Detail | Current: Range Limits(NAMUR NE43 Out of Range):Below 3.8 mA or above 20.5 mA for 4 to 20 mA output; 0 mA or above 20.5 mA for 0 to 20 mA output Sensor Error Detection(Dip Switch Selectable for Enable or None): Below 3.5 mA or above 23 mA for 4 to 20 mA output; 0 mA or above 23 mA for 0 to 20 mA output Incorrect DIP-Switch Setting Identification: Below 3.5 mA or above 23 mA for 4 to 20 mA output; 0 mA or above 23 mA for 0 to 20 mA output Output Error Level: DIP switch selectable for upscale or downscale. Voltage: Range Limits (Out of Range):Range ±2.5% Sensor Error Detection (Dip Switch Selectable for Enableor None): 0V or selected range + 10% Incorrect DIP-Switch Setting Identification: 0V Output Error Level: DIP switch selectable for upscale or downscale |
Output Signal | Current, Voltage |
Output Value | Process |
Power Consumption | 0.7 W, Internal - 0.65 W |
Relative Humidity | 0 to 95% RH (non-condensing) |
Response Time | < 30 ms |
Response Time Note | Response Time (0 to 90%, 100 to 10%): <30 ms/300 ms (selectable, provides either fast response or signal dampening as needed) |
Screw Terminal Torque | 0.5 Nm |
Stability | Load Stability: ≤0.01% of span/100 Ω |
Storage Temperature, Max | 85 °C |
Storage Temperature, Min | -40 °C |
Supply Power Note | 16.8 to 31.2 Vdc via connectors |
Supply Power Type | DC |
Supply Voltage | 16.8 to 31.2 Vdc |
Temperature Coefficient | ≤±0.02°C/°C |
Voltage Output Range | 0 to 10 Vdc |
Weight | 70 g |
Width | 6.1 mm |
Wire Gauge | 26 to 13 AWG |
See All Specs |
PDFs & Manuals
Show Ratings & Reviews
Rated 5 out of
5
by
Qaiser from
Excellent accuracy
I bought this to be used in a test lab where temperature accuracy is 0.1C and the DRSL has stood up to the expectation. Excellent accuracy, stability, form factor and ease of use.
Date published: 2019-05-14