Welcome to our new website, found an issue or bug? Please report it here

D1000-Series
Standard Digital Modules for Signal Conditioning, Scaling, and Sensor Integration
Models In Stock
- Complete Sensor To RS-232C or RS-485 Interface
- Input Modules for Thermocouples, RTDs, Voltages, Currents, Pulse and Frequency, and Bridge Inputs
- Isolated Inputs
- RS-485 Format Permits Remote Communications Up to Four Thousand Feet
D1000-Series
From
C$
397.44
Models In Stock

Product Overview
- Accuracy ±0.01 % of reading ±10 µs
- Baud Rate 300 to 38,400
- Data Interface Note Up to 124 multidrop modules per communications port, ASCII Format command/ response protocol, Can be used with ‘dumb’ terminal, Parity options: odd, even, none, All communications setups stored in memory, Checksum can be added to any command or response, user selectable channel address
- Digital Output Open collector to 30V,100 mA max load
- Electrical Connection Screw Terminal
- Frequency Input Range 1 Hz to 20 kHz
- Height 6.223 mm
- Input Control Signal ±100 Vdc
- Length 9.144 mm
- Materials ABS
- Operating Temperature, Max 70 °C
- Operating Temperature, Min -25 °C
- Output Signal Digital
- Protection Input Protection: 250 Vac
- Relative Humidity 0 to 95% RH non-condensing
- Storage Temperature, Max 85 °C
- Storage Temperature, Min -25 °C
- Supply Power Type DC
- Supply Voltage 10 to 30 Vdc, 0.75 W
- Width 2.794 mm
The D1000 and D2000 Series digital transmitters are a complete family of easy to use interface modules for personal computers and other processor based equipment with standard serial I/O ports. The modules convert analog input signals to engineering units and transmit, in ASCII format, to any host computer with a standard RS-232C or RS-485 port. This modular design enables anyone familiar with a personal computer to construct a flexible and cost effective data acquisition system. These modules can measure temperature, pressure, flow, voltages, currents and various types of digital signals.
The D1000 series provide direct interface to a wide variety of sensors and perform all signal conditioning, scaling, linearization and conversion to engineering units.
Each module also provides digital I/O lines for controlling devices through solid state relays or TTL signals. These digital I/O lines along with integral limit setting capability provide alarm and control outputs. With the exception of the D1400 RTD and D1500 bridge modules, every D1000 module contains an on-board event counter. The event counter will count up to ten million transitions on the digital input line. All user selectable options (address, baud rate, alarms, etc.) are done through the communications port and stored in nonvolatile memory thereby eliminating switches or external adjustments of any kind.
The D2000 series of user programmable data acquisition and control modules allow direct interface of non-linear analog sensors to computers with serial I/O ports. Use of these modules enables downloading up to 23 breakpoints through the communications port. With these breakpoints the user can program a module to virtually any transfer function.
Ranges for D1000 Modules
Ranges for D2000 Modules
Software
A utility software package is available at no additional charge for the D1000 and D2000 family of products. This software provides program examples and a simple data logging program. The software may be downloaded from this web site from the "Software" link in the "Related Links" section at the bottom of this page.
The D1000 series provide direct interface to a wide variety of sensors and perform all signal conditioning, scaling, linearization and conversion to engineering units.
Each module also provides digital I/O lines for controlling devices through solid state relays or TTL signals. These digital I/O lines along with integral limit setting capability provide alarm and control outputs. With the exception of the D1400 RTD and D1500 bridge modules, every D1000 module contains an on-board event counter. The event counter will count up to ten million transitions on the digital input line. All user selectable options (address, baud rate, alarms, etc.) are done through the communications port and stored in nonvolatile memory thereby eliminating switches or external adjustments of any kind.
The D2000 series of user programmable data acquisition and control modules allow direct interface of non-linear analog sensors to computers with serial I/O ports. Use of these modules enables downloading up to 23 breakpoints through the communications port. With these breakpoints the user can program a module to virtually any transfer function.
Ranges for D1000 Modules
|
|
|
|
|
|
Bridge Inputs | ||
RS-232 Output | RS485 Output | Description |
D1511 | D1512 | 30 mV input, 5V excitation |
D1521 | D1522 | 30 mV input, 10V excitation |
D1531 | D1532 | 100 mV input, 5V excitation |
D1541 | D1542 | 100 mV input, 10V excitation |
D1561 | D1562 | 1 to 6V input, 10V excitation |
Ranges for D2000 Modules
|
|
|
|
Software
A utility software package is available at no additional charge for the D1000 and D2000 family of products. This software provides program examples and a simple data logging program. The software may be downloaded from this web site from the "Software" link in the "Related Links" section at the bottom of this page.
PDFs & Manuals
Show Ratings & Reviews
Rated 5 out of
5
by
Brauner from
100% OK.
Product arrived on time . All 100% ok. We recommend.
Date published: 2024-07-31